Datasheet

2
WIDE APPLICATION COVERAGE - 600 V TO 5 KV APPARATUS
600 V Class, 3-phase Electrical Apparatus
The HVD310x probes are available in a range of bandwidths from 25 to 120 MHz with standard 2 meter cable (6 meter
cable model available). All probes have industry best CMRR for best noise-immunity, are guaranteed to 1% gain accuracy,
and have the industry’s widest differential voltage range in a 1 kV rated high voltage differential probe.
Only 1 kV safety rated probe that
serves the full 600 V class requirement
1500 V differential range with
industry’s best overshoot
measurement capability (to 2000 V
pk
)
Industry’s best offset capability
(1500 V) when used with HDO Series
oscilloscopes
Bandwidth rating up to 120 MHz
6 meter cable model available
(HVD3106-6M)
Ideal voltage range and performance
for Gate drive probing
Models available without accessories
for a lower cost (HVD310x-NOACC)
5 kV Class, 3-phase Electrical Apparatus
The HVD3605 probe is safety-rated for 6000 V
rms
and 8485 V(DC + peak AC) for full coverage of 5 kV class apparatus. The
probe has ample 100 MHz of bandwidth, is standard with a 6 meter cable, is guaranteed to 1% gain accuracy, has excellent
CMRR, and has the industry’s widest differential voltage range.
Only probe that permits AC Line,
DC Bus, and Drive/Inverter output
voltage probing through
4160 V apparatus ratings
Industry’s best overshoot
measurement capability
(to 7600 V
pk
)
Industry’s best offset capability
(6000 V) when used with
HDO Series oscilloscopes
Standard 6 meter cable
*Based on 50% overshoot condition
*Based on 25% overshoot condition
Sinusoidal AC
Line Input
DC Bus
Voltage
Drive / Inverter
Pulse-Width Modulated (PWM) Output
V
rms
or
V
ac
V
pk-pk
V
dc
V
pk
(Rated) V
pk
(with Overshoot)*
Line-Line
Line-
Neutral
Line-Line
Line-
Neutral
Line-Line
Line-
Neutral
400 1131 653 566 566 327 849 491
480 1358 784 679 679 392 1019 588
600 1697 980 849 849 490 1274 735
690 1952 1127 976 976 563 1464 845
Sinusoidal AC
Line Input
DC Bus
Voltage
Drive / Inverter
Pulse-Width Modulated (PWM) Output
V
rms
or
V
ac
V
pk-pk
V
dc
V
pk
(Rated) V
pk
(with Overshoot)*
Line-Line
Line-
Neutral
Line-Line
Line-
Neutral
Line-Line
Line-
Neutral
2400 6788 3920 3395 3395 1960 4244 2450
3300 9334 5388 4666 4666 2694 5833 3368
4160 11766 6794 5884 5884 3397 7355 4246