® ® CONNECTING THE FUTURE 1 MON OUT IN 4 8 12 16 20 24 28 MON 32 36 OUT 40 44 IN 48 52 NE-2 56 60 64 MON OUT IN NE-1 MON OUT IN DIGITAL NETWORK INTERFACE-1B USER MANUAL 108891 Issue A Rev 2
Digital Network Interface 1-B User Manual Document Number 108891 Issue A Rev 2 Copyright© Telect, Inc., 1998, All Rights Reserved. Telect and Connecting the Future are registered trademarks of Telect, Inc., 2111 N. Molter Rd., Liberty Lake, Washington 99019 Note: Telect assumes no liability from the application or use of these products. Neither does Telect convey any license under its patent rights nor the patent rights of others.
INSIDE OF BACK COVER
Contents Section 1 Descriptions DNI-1B ........................................................................................ 1-1 Capabilities ............................................................................ 1-1 Features .................................................................................. 1-2 System-Level Applications.......................................................... 1-2 Main Assemblies..........................................................................
Section 5 Service Owner Maintenance ..................................................................... 5-1 In Case Of Difficulty ................................................................... 5-1 In-Warranty Service ..................................................................... 5-1 Out-Of-Warranty Service............................................................. 5-2 Repacking For Shipment ............................................................. 5-2 iv Telect, Inc.
1 Descriptions DNI-1B Telect’s Bantam Digital Network Interface Panel—the DNI-1B, PN 0107128-5001 (128 circuit) and 010-7112-5001 (112 circuit)—is a central interface point for networks that connect DS-1 signals from digital crossconnect system (DCS) circuits to network element (NE) circuits. As an extension to the backplane of DCS equipment, the DNI-1B allows circuit configuration changes, maintenance, and troubleshooting without disrupting DCS operation.
Descriptions DNI-1B User Manual Features • • • • • • DDJ™ tri-jacks for IN, OUT, and MON ports Each circuit has two tri-jacks—one for DCS (NE-1) and one for network element (NE-2) circuits Circuit designation labels Hinged designation holders Four wire-wrap termination points for both NE-1 and NE-2 Two wire-management tie-down bars SYSTEM-LEVEL APPLICATIONS DNI-1B Digital Switch 1:0 DCS Office Repeater Bays (ORBs) DS-1 Cables DS-1 Cables 3:1 DCS DS-3 Cable Channel Banks Fiber Optic Transmission Sy
DNI-1B User Manual Descriptions Termination Point ® NE-2 T OUT R T IN R NE-1 T OUT R T IN R SPOKANE, WA. ® SPOKANE, WA. 64 60 56 52 48 64 60 56 52 48 Tie-Down Bar PHYSICAL SPECIFICATION 15 lb (6.8 kg) Issue A Rev 2 108891 Telect, Inc.
2 Installation INSTALLATION CONSIDERATIONS Location and Space DNI-1B mounts flush into both unequal flange and equal flange (EIA or WECO) racks/bays—the 112-circuit version in 19" (48.3 cm) bays, the 128—circuit version in 23" (58.4 cm) bays. Rack configuration is limited mainly by the number of cables a bay can accommodate. Telect recommends a maximum of 22 DNI-1B panels per bay: • • • Allows easy access for maintenance. Keeps the panels within reach. Provides enough room for cable routing.
Installation DNI-1B User Manual DCS Terminations Panels Total Cables 88 Cable Space Needed per Side of Bay (in.2) EIA Bay Spaces Required 27.28 22 128 112 641–704 561–616 11 705–768 617–672 12 96 29.76 24 769–832 673–728 13 104 32.24 26 833–896 729–784 14 112 34.72 28 897–960 785–840 15 120 37.20 30 961–1024 841–896 16 128 39.68 32 1025–1088 897–952 17 136 42.16 34 1089–1152 953–1008 18 144 44.64 36 1153–1216 1009–1064 19 152 47.
DNI-1B User Manual Installation Network Bay Extender Panel Telect recommends network bay extender panels for cable management— two for each fully provisioned DNI-1B bay. The extender provides 81 square inches (522.6 square cm) of routing space (enough for 135 30-pair ABAM cables) and 9 cable management brackets to secure and channel the cables. Extender Cable Management Bracket (Inside the Extender) Tools and Equipment Back View of Network Bay No special tools or equipment are required.
Installation DNI-1B User Manual INSTALLATION PROCEDURE Mounting the DNI-1B Step Action 1. Align the DNI-1B chassis mounting holes with the mounting holes of the network bay/rack. 2. Install four mounting screws (two on each side) into the mounting holes but do not completely tighten them. 3. Attach the hinged label holders to the front of the panel. a. Slip the eyehole in the center of the holder over the head of the top mounting screw. b.
DNI-1B User Manual Issue A Rev 2 Installation 6. Repeat Steps 2–5 for the DCS OUT cables, connecting them to the NE-1 OUT termination points. 7. Route the NE IN cables to the same side of the network bay as the DCS IN cables and the NE OUT cables to the same side as the DCS OUT cables. Tie-wrap the cables in place within the extender panel cable management brackets. 8.
3 Electrical Operation DCS wires attach to the lower four wire-wrap termination points on the rear of the DNI-1B panel (NE-1); the network element wires attach to the upper four points (NE-2). OUT (transmit) circuits attach to the upper pair of termination points; IN (receive) circuits attach to the lower pair.
Electrical Operation DNI-1B User Manual Inserting a Bantam plug into the jack does the following: Plug Jack Function Single NE-1 MON NE-2 MON Accesses DCS OUT circuit Accesses NE OUT circuit Dual Patch NE-1 OUT/IN NE-2 OUT/IN Patches DCS or NE circuit Patches DCS or NE circuit Insulators Tip Ring Ground Out In 3-2 Telect, Inc.
4 User Functions PATCHING Step Action 1. Partially insert a dual Bantam patch-cord in the OUT and IN jacks of the appropriate NE-2 circuit on the front of the DNI1-B panel: OUT Side View of DNI1-B Panel Curved Side IN 2. Twist the plug on the other end of the cord so that its curved side is in the opposite orientation—if the first plug’s curved side is up, the second plug’s must be down. This is how you connect the IN of one circuit to the OUT of another.
User Functions DNI-1B User Manual 3. Partially insert the second plug in the OUT and IN jacks of the appropriate NE-1 circuit. 4. Simultaneously push both plugs fully into the jacks. LOOPBACK To temporarily loop an NE or DCS OUT port to its IN port, fully insert a Bantam looping plug into the jacks of the appropriate circuit. OUT Side View of DNI1-B Panel Signal Path IN MONITORING You can monitor NE and DCS circuit outputs from the front of the DNI-1B panel.
DNI-1B User Manual User Functions DROP-AND-INSERT TEST Terminate a T-1 signal at the panel with a 100 ohm DNI-1B terminating plug. Fully insert the plug into the jack of the appropriate NE-1 or NE-2 circuit. Side View of DNI1-B Jack Issue A Rev 2 108891 Telect, Inc.
5 Service OWNER MAINTENANCE Telect’s DNI-1B does not need preventive maintenance. IN CASE OF DIFFICULTY If problems occur after initial installation, check all cable connections and the installation instructions in Section 2. IN-WARRANTY SERVICE Contact your Telect equipment distributor, or call a Telect Customer Service Representative: 1-800-551-4567 1-509-926-6000 Telect will repair or replace defective products within the limits of the warranty. See “Repacking for Shipment” in this section.
Service DNI-1B User Manual OUT-OF-WARRANTY SERVICE The procedure for out-of-warranty service is the same as for in-warranty service, except that Telect charges a processing fee, and you must submit a Purchase Order along with a Return Material Authorization (RMA) before returning equipment. Call a Customer Service Representative for help getting these forms. The processing fee guarantees a repair estimate and is credited against actual material and labor costs. REPACKING FOR SHIPMENT Step Action 1.
Telect, Inc. 2111 N. Molter Rd. P.O. Box 665, Liberty Lake, WA 99019 509-926-6000, 800-551-4567, Fax 509-926-8915 E-mail: getinfo@telect.com Internet: http://www.telect.