G2ZMF11
Functions
Connections Dimensions
Flasher pulse first (Bi20)
When the supply voltage U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED flashes). After the interval t has expired, the output relay
switches into off-position (yellow LED not illuminated) and the set
interval t begins again.
The output relay is triggered at a ratio of 1:1 until the supply voltage
is interrupted
Flasher pause first (Bp20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired, the output relay R
switches into on-position (yellow LED illuminated) and the set interval
t begins again. After the interval t has expired, the output relay switch-
es into off-position (yellow LED not illuminated).
The output relay is triggered at a ratio of 1:1 until the supply voltage is
interrupted.
Single shot trailing edge with control contact (Wa20)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
Closing the control contact S has no influence on the condition of the
output relay R. When the control contact is opened, the output relay
switches into on-position (yellow LED illuminated) and the set interval
t begins (green LED flashes). After the interval t has expired (green
LED illuminated), the output relay switches into off-position (yellow
LED not illuminated).
During the interval, the control contact can be operated any number
of times.
A further cycle can only be started when the cycle run has been com-
pleted.