Datasheet
Subject to alterations and errors
G2ZMF11
Functions
ON delay (E20)
When the supply voltage U is applied, the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay R switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t,
the interval already expired is erased and is restarted when the sup-
ply voltage is next applied.
OFF delay with control contact (R20)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, the output relay R switches into
on-position (yellow LED illuminated). If the control contact is opened,
the set interval t begins (green LED flashes). After the interval t has
expired (green LED illuminated) the output relay switches into off-po-
sition (yellow LED not illuminated).
If the control contact is closed again before the interval t has expired,
the interval already expired is erased and is restarted with the next
cycle.
Flasher pulse first (Bi11)
When the supply voltage U is applied, the instantaneous contact and
the delayed contact switch into on-position (yellow LED illuminated)
and the set interval t begins (green LED flashes). After the interval
t has expired, the delayed contact switches into off-position (yellow
LED not illuminated) and the set interval t begins again.
The delayed contact is triggered at a ratio of 1:1 until the supply volt-
age is interrupted.
ON delay with control contact (Es20)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the output relay R switches into on-position (yellow LED illuminated).
This status remains until the control contact is opened again.
If the control contact is opened before the interval t has expired, the
interval already expired is erased and is restarted with the next cycle.
Flasher pause first (Bp11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired, the delayed contact switches
into on-position (yellow LED illuminated) and the set interval t begins
again. After the interval t has expired, the delayed contact switches
into off-position (yellow LED not illuminated).
The delayed contact is triggered at a ratio of 1:1 until the supply volt-
age is interrupted.
Single shot leading edge with control contact (Ws20)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED flashes). After the interval t has expired (green LED il-
luminated) the output relay switches into off-position (yellow LED not
illuminated).
During the interval, the control contact can be operated any number
of times.
A further cycle can only be started when the cycle run has been com-
pleted.
Single shot leading edge voltage controlled (Wu20)
When the supply voltage U is applied, the output relay R switches
into on-position (yellow LED illuminated) and the set interval t begins
(green LED flashes). After the interval t has expired (green LED illumi-
nated) the output relay switches into off-position (yellow LED not illu-
minated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the interval t has expired,
the output relay switches into off-position. The interval already expired
is erased and is restarted when the supply voltage is next applied.