Datasheet
Subject to alterations and errors
Technical data
G2ZMF11
9. Accuracy
Base accuracy: ±1% (of maximum scale value)
using 1MΩ remote potentiometer
Frequency response: -
Adjustment accuracy: ≤5% (of maximum scale value)
using 1MΩ remote potentiometer
Repetition accuracy: <0.5% or ±5ms
Voltage influence: -
Temperature influence: ≤0.01% / °C
Functions
The internal potentiometer is de-activated when a remote-potentio-
meter is connected !
The function has to be set before connecting the relay to the supply
voltage.
ON delay (E11)
When the supply voltage U is applied, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into on-position (yellow LED illuminated).
This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the expiry of the interval t,
the interval already expired is erased and is restarted when the sup-
ply voltage is next applied.
OFF delay with control contact (R11)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, both contacts switch into on-
position (yellow LED illuminated). If the control contact is opened, the
instantaneous contact switches into off-position and the set interval
t begins (green LED flashes). After the interval t has expired (green
LED illuminated) the delayed contact switches into off-position (yellow
LED not illuminated).
If the control contact is closed again before the interval t has expired,
the interval already expired is erased and is restarted with the next
cycle.
Single shot trailing edge with control contact (Wa11)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed the instantaneous contact
switches into on-position. When the control contact is opened, the
instantaneous contact switches into off-position, the delayed contact
switches into on-position (yellow LED illuminated) and the set interval
t begins (green LED flashes). After the interval t has expired (green
LED illuminated), the delayed contact switches into off-position (yel-
low LED not illuminated).
During the interval, the control contact (and the instantaneous con-
tact) can be operated any number of times.
A further cycle can only be started when the cycle run has been com-
pleted.
ON delay with control contact (Es11)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, the instantaneous contact
switches into on-position and the set interval t begins (green LED
flashes). After the interval t has expired (green LED illuminated) the
delayed contact switches into on-position (yellow LED illuminated).
This status remains until the control contact is opened again.
If the control contact is opened before the interval t has expired, the
interval already expired is erased and is restarted with the next cycle.
Single shot leading edge with control contact (Ws11)
The supply voltage U must be constantly applied to the device (green
LED illuminated).
When the control contact S is closed, both contacts switch into on-
position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the delayed contact switches into off-position (yellow LED not illumi-
nated). The instantaneous contact remains in on-position, until the
control contact is opened again.
During the interval, the control contact (and the instantaneous con-
tact) can be operated any number of times.
A further cycle can only be started when the cycle run has been com-
pleted.
Single shot leading edge voltage controlled (Wu11)
When the supply voltage U is applied, both contacts switch into on-
position (yellow LED illuminated) and the set interval t begins (green
LED flashes). After the interval t has expired (green LED illuminated)
the delayed contact switches into off-position (yellow LED not illumi-
nated). This status remains until the supply voltage is interrupted.
If the supply voltage is interrupted before the interval t has expired,
the both contacts switch into off-position. The interval already expired
is erased and is restarted when the supply voltage is next applied.
10. Ambient conditions
Ambient temperature: -25 to +55°C (according to IEC 68-1)
-25 to +40°C (according to UL 508)
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85%
(according to IEC 721-3-3 class 3K3)
Pollution degree: 3 (according to IEC 664-1)
Vibration resistance: 10 to 55Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance: 15g 11ms (according to IEC 68-2-27)