Timers - GAMMA series
16 functions
16 time ranges
Connection of remote potentiometer possible
Supply voltage selectable via power modules
2 change over contacts
Width 22.5mm
Industrial design
Technical data
1. Functions
1 delayed contact (terminals 15-16-18) and
1 instantaneous contact (terminals 25-26-28)
E11 ON delay
R11 OFF delay with control contact
Es11 ON delay with control contact
Wu11 Single shot leading edge voltage controlled
Ws11 Single shot leading edge with control contact
Wa11 Single shot trailing edge with control contact
Bi11 Flasher pulse first
Bp11 Flasher pause first
2 delayed contacts
E20 ON delay
R20 OFF delay with control contact
Es20 ON delay with control contact
Wu20 Single shot leading edge voltage controlled
Ws20 Single shot leading edge with control contact
Wa20 Single shot trailing edge with control contact
Bi20 Flasher pulse first
Bp20 Flasher pause first
2. Time ranges
Time range Adjustment range
1s 50ms 1s
3s 150ms 3s
10s 500ms 10s
30s 1500ms 30s
1min 3s 1min
3min 9s 3min
10min 30s 10min
30min 90s 30min
1h 3min 1h
3h 9min 3h
10h 30min 10h
30h 90min 30h
1d 72min 1d
3d 216min 3d
10d 12h 10d
30d 36h 30d
3. Indicators
Green LED ON: indication of supply voltage
Green LED flashes: indication of time period
Yellow LED ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: any
Shockproof terminal connection according to VBG 4
(PZ1 required), IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
12 to 400V AC terminals A1-A2 (galvanically separated)
selectable via power modules TR2
Tolerance: according to specification of power module
Rated frequency: according to specification of power module
Rated consumption: 2VA (1.5W)
Duration of operation: 100%
Reset time: 100ms
Residual ripple for DC: -
Drop-out voltage: >30% of the supply voltage
Overvoltage category: III (according to IEC 60664-1)
Rated surge voltage: 4kV
6. Output circuit
2 potential free change over contacts
Rated voltage: 250V AC
Switching capacity (distance <5mm): 750VA (3A / 250V AC)
Switching capacity (distance >5mm): 1250VA (5A / 250V AC)
Fusing: 5A fast acting
Mechanical life: 20 x 10
6
operations
Electrical Life: 2 x 10
5
operations
at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category: III (according to IEC 60664-1)
Rated surge voltage: 4kV
7. Control contact
Activation: bridge Y1-Y2
Potential free: yes, basic isolation against input
and output circuit
Loadable: no
Control voltage: max. 5V
Short circuit current: max. 1mA
Line length: max. 10m
Control pulse length: min. 50ms
8. Remote potentiometer (not included)
The internal potentiometer is de-activated when a remote potentio-
meter is connected !!!
Connections: 1MΩ potentiometer (type RONDO R2),
terminals Z1-Y2
Line type: twisted pair
Control voltage: max. 5V
Short circuit current: max. 5µA
Line length: max. 5m
G2ZMF11