Datasheet

MONITORING RELAY / 1-PHASE CURRENT
V4IM100AL20
Art.Nr.: 2104400
V4IM100AL20P
Art.Nr.: 2104410
Page 3 of 8
OUTPUT CIRCUIT
Endurance
mechanical
30 x 10
6
switching cycles
electrical (AC-1)
100 x 10
3
switching cycles
Rated frequency of operation
with load
6/min
without load
1200/min
Fuse rating 8 A fast acting
ACCURACY
Base accuracy
DC, AC Sinus
50/60 Hz
< 2 %
AC Sinus
16,6 … 400 Hz
< 2,5 %
CF < 2,8 @ 50 Hz
I peak max = 175A
< 5 %
Setting accuracy < 5 % (of full scale)
Repeat accuracy < 1 %
Temperature inuence < 0,04 % / °C
Voltage inuence -
Frequency inuence -
Damp inuence
> 85 % rel.
humidity
+3 % of base accuracy
ENVIRONMENTAL CONDITIONS
Ambient temperature
operation
-25 … +60°C
storage
-40 … +70°C
Relative humidity 5 … 95 %
Vibration
EN 60947-1
2 … 13,2 Hz: 1 mm; 13,2 … 100 Hz: 7 m/s
2
Shock
EN 60947-1
150 m/s
2
11 ms
GENERAL DATA
Dimensions
W × H × D
45 x 67 x 76 mm
Ø Built-in current
transformer
14,5 mm
Mounting DIN rail (EN60715)
Mounting position any
Housing material PA 66, self-extinguishing plastic, class V-0
Degree of protection
housing
IP40
terminals
IP20
Electrical connection
V4IM...20
Screw terminal
Wire size
exible with wire
end ferrule
0,5 … 2,5 mm² (20 AWG … 13 AWG)
exible without
wire end ferrule
0,5 … 4 mm² (20 AWG … 12 AWG)
rigid
0,5 … 4 mm² (20 AWG … 12 AWG)
http://tele-online.com
VEO