Datasheet

MONITORING RELAY / 3-PHASE VOLTAGE
V2PM400Y/230VS10
Art.Nr.: 2100500
V2PM400Y/230VS10P
Art.Nr.: 2100510
Page 3 of 7
MEASURING CIRCUIT
Endurance
mechanical
30 x 10
6
switching cycles
electrical (AC-1)
100 x 10
3
switching cycles
Rated frequency of operation
with load
6/min
without load
1200/min
Fuse rating 8 A fast acting
ACCURACY
Base accuracy < 2,5 %
Setting accuracy < 5 % (of full scale)
Repeat accuracy < 1%
Temperature inuence < 0,01 % / °C
Voltage inuence -
Frequency inuence < 0,003 % / Hz
ENVIRONMENTAL CONDITIONS
Ambient temperature
operation
-25 … +60°C
storage
-40 … +70°C
Relative humidity 5 … 95 %
Vibration
EN 60947-1
2 … 13,2 Hz: 1 mm; 13,2 … 100 Hz: 7 m/s
2
Shock
EN 60947-1
150 m/s
2
11 ms
GENERAL DATA
Dimensions
W × H × D
22,5 x 67 x 76 mm
Mounting DIN rail (EN60715)
Mounting position any
Housing material PA 66, self-extinguishing plastic, class V-0
Degree of protection
housing
IP40
terminals
IP20
Electrical connection
V2PM...10
screw terminal
Wire size
exible with wire
end ferrule
0,5 … 2,5 mm² (20 AWG … 13 AWG)
exible without
wire end ferrule
0,5 … 4 mm² (20 AWG … 12 AWG)
rigid
0,5 … 4 mm² (20 AWG … 12 AWG)
Stripping length 8 mm
Tightening torque max. 1Nm
http://tele-online.com
VEO