Datasheet
MONITORING RELAY / 3-PHASE VOLTAGE
V2PM400Y/230VS10
Art.Nr.: 2100500
V2PM400Y/230VS10P
Art.Nr.: 2100510
Page 2 of 7
MEASURING CIRCUIT
Thresholds
Max
75 … 130 %
Min
70 … 125 %
Asymmetry
-
Hysteresis 1 %
TIMING CIRCUIT
Start-up delay
xed
approx. 200ms
Tripping delay
adjustable
0,1 ... 10 s
phase sequence
approx. 65 ms at 50 Hz
RANGE OF FUNCTIONS
Functions
4
U, W, U+S, W+S
STATUS INDICATION
Relay status
LED R (yellow) on
output relay energized
Voltage monitor
LED MAX (red) on
indication of overvoltage
LED MAX (red)
ashes
indication of tripping delay for overvoltage
LED MIN (red) on
indication of undervoltage
LED MIN (red)
ashes
indication of tripping delay for undervoltage
LED UFail. (red) on
indication of phase sequence failure or phase loss
LED UFail. (red)
ashes
indication of tripping delay for phase loss
OUTPUT CIRCUIT
Terminals 15-16-18
Kind of output Relay
Number of contacts
change-over
contact
1
Contact material AgNi
Rated voltage
(IEC 60947-1)
250 V
Maximum switching voltage 400 V AC
Minimum switching voltage / switching current 12 V / 10 mA
Rated current
(IEC 60947-5-1)
AC-1
8 A / 250 V
AC-15
1,5 A / 240 V (B300)
DC-12
8 A / 24 V
DC-13
0,1 A / 250 V
http://tele-online.com
VEO