Datasheet
MONITORING RELAY / 1-PHASE CURRENT
V2IM10AL10
Art.Nr.: 2100400
V2IM10AL10P
Art.Nr.: 2100410
Page 5 of 7
U
LED U
LED Max
LED Min
I
Max
Delay
R
Delay
I
Min
e
Fehlerspeicher aktiv / Latch active
U
LED U
LED Max
LED Min
I
Max
Delay
R
Delay
I
Min
Fehlerspeicher aktiv / Latch active
Overcurrent monitoring (O)
When the supply voltage U is applied, the output relay R
switches into on-position if the measured current is below the
adjusted threshold I
Max
. When the measured current exceeds
the adjusted threshold I
Max
, the set interval of the tripping
delay (DELAY) begins. After the interval has expired, the output
relay R switches into o-position. The output relay R switches
into on-position again, as soon as the measured current falls
below the adjusted threshold I
Min
.
Undercurrent monitoring (U)
When the supply voltage U is applied, the output relay R
switches into on-position if the measured current is beyond
the adjusted threshold I
Max
. When the measured current
falls below the adjusted threshold I
Min
, the set interval of the
tripping delay (DELAY) begins. After the interval has expired,
the output relay R switches into o-position. The output relay
R switches into on-position again, as soon as the measured
current exceeds the adjusted threshold I
Max
.
Window function (W)
When the supply voltage U is applied, the output relay R
switches into on-position if the measured current is within the
adjusted thresholds I
Min
and I
Max
. When the measured
current falls below the adjusted threshold I
Min
, the set interval
of the tripping delay (DELAY) begins. After the interval has
expired, the output relay R switches into o-position. The
output relay R switches into on-position again, as soon as the
measured current exceeds the adjusted threshold I
Min
. When
the measured current exceeds the adjusted threshold I
Max
,
the set interval of the tripping delay (DELAY) begins again.
After the interval has expired, the output relay R switches
into o-position. The output relay R switches into on-position
again, as soon as the measured current falls below the adjus-
ted threshold I
Max
.
Fault latch
If the fault latch is activated and a failure has occurred, this
failure is stored. The failure can only be reset by interrupting
the supply voltage.