Datasheet

MONITORING RELAY / 1-PHASE CURRENT
V2IM10AL10
Art.Nr.: 2100400
V2IM10AL10P
Art.Nr.: 2100410
Page 1 of 7
TECHNICAL DATA
SUPPLY CIRCUIT
Terminals Li-N
Supply voltage
AC
110 … 240 V
DC
24 ... 240 V
Supply voltage tolerance
AC
-15 / +15 %
DC
-30 / +30 %
Rated frequency 16,6 ... 400 Hz or DC
Rated frequency tolerance 16,0 … 420 Hz
Rated consumption
230 V AC
0,37 W / 1,3 VA
24 V DC
0,25 W / 0,25 VA
Duty-cycle 100 %
Backup power time < 140 ms
Recovery time > 200 ms
Drop-out voltage ≥ 6 V
MEASURING CIRCUIT
Terminals Li-Lk
Measurand current 1-phase
Measuring method True RMS
Monitoring function underurrent (U), overcurrent (O), window (W)
Measuring range 10 A AC/DC
AC/DC current monitoring
Multifunction
Supply voltage 24-240V DC or
110-240V AC
1 change-over contact
Width 22,5 mm
Control element
Tripping delay
Maximum threshold
Minimum threshold
Function selector
Status indication
LED U: Supply voltage
LED Max: Overcurrent
LED Min: Undercurrent
LED R: Relay status
http://tele-online.com
VEO

Summary of content (7 pages)