Datasheet
MONITORING RELAY / 1-PHASE VOLTAGE
V2UM230V10
Art.Nr.: 2100300
V2UM230V10P
Art.Nr.: 2100310
Page 2 of 7
MEASURING CIRCUIT
Overload capacity see supply voltage tolerance
Thresholds
Max
80 … 115 %
Min
75 … 110 %
Hysteresis 1 %
TIMING CIRCUIT
Start-up delay
xed
approx. 300 ms
Tripping delay
adjustable
0,1 ... 10 s
RANGE OF FUNCTIONS
Functions
2
U, W
STATUS INDICATION
Supply voltage
LED U (green) on
supply voltage applied
Relay status
LED R (yellow) on
output relay energized
Voltage monitor
LED MAX (red) on
indication of overvoltage
LED MAX (red)
ashes
indication of tripping delay for overvoltage
LED MIN (red) on
indication of undervoltage
LED MIN (red)
ashes
indication of tripping delay for undervoltage
OUTPUT CIRCUIT
Terminals 15-16-18
Kind of output Relay
Number of contacts
change-over
contact
1
Contact material AgNi
Rated voltage
(IEC 60947-1)
250 V
Maximum switching voltage 400 V AC
Minimum switching voltage / switching current 12 V / 10 mA
Rated current
(IEC 60947-5-1)
AC-1
8 A / 250 V
AC-15
1,5 A / 240 V (B300)
DC-12
8 A / 24 V
DC-13
0,1 A / 250 V
Endurance
mechanical
30 x 10
6
switching cycles
electrical (AC-1)
100 x 10
3
switching cycles
http://tele-online.com
VEO