Datasheet
MONITORING RELAY / 3-PHASE VOLTAGE
V2PF480Y/277VSY01
Art.Nr.: 2100000
V2PF480Y/277VSY01P
Art.Nr.: 2100010
MEASURING CIRCUIT
Thresholds
Max
-
Min
-
Asymmetry
5 ... 25 %, OFF
Hysteresis -
TIMING CIRCUIT
Start-up delay
xed
approx. 400 ms
Tripping delay < 250 ms
STATUS INDICATION
Supply voltage
LED U (green) on
supply voltage applied
Relay status
LED R (yellow) on
output relay energized
OUTPUT CIRCUIT
Terminals 11-12-14
Kind of output Relay
Number of contacts
change-over
contact
1
Contact material AgNi
Rated voltage
(IEC 60947-1)
250V
Maximum switching voltage 400V AC
Minimum switching voltage / switching current 12 V / 10 mA
Rated current
(IEC 60947-5-1)
AC-1
8 A / 250 V
AC-15
1,5 A / 240 V (B300)
DC-12
8 A / 24 V
DC-13
0,1 A / 250 V
Endurance
mechanical
30 x 10
6
switching cycles
electrical (AC-1)
100 x 10
3
switching cycles
Rated frequency of operation
with load
6/min
without load
1200/min
Fuse rating 8 A fast acting
ACCURACY
Base accuracy < 5 % (of full scale)
Setting accuracy < 5 % (of full scale)
Repeat accuracy < 1 %
Temperature inuence < 0,05 % / °C
http://tele-online.com Page 2 of 7
VEO