Datasheet

Subject to alternations and errors
Release 10/05
Timers - ENYA series
Timers multifunctional
Up to 7 functions
7 time ranges
Wide input voltage range
1 change over contact
Width 17.5 mm
Installation design
Technical data
1. Functions
The function has to be set before connecting the relay to the supply
voltage.
E ON delay
R OFF delay
Ws Single shot leading edge with control input
Wa Single shot trailing edge with control input
Es ON delay with control input
Wu Single shot leading edge voltage controlled
Bp Flasher pause first
Function sets of the distinct types are according to table
ordering information or printing on the unit.
2. Time ranges
Time range Adjustment range
1s 50ms 1s
10s 500ms 10s
1min 3s 1min
10min 30s 10min
1h 3min 1h
10h 30min 10h
100h 5h 100h
3. Indicators
Green LED U/t ON: indication of supply voltage
Green LED U/t flashes: indication of time period
Yellow LED R ON/OFF: indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage: terminals A1(+)-A2
Types E1Z..12-240VAC/DC: 12 to 240V AC/DC
Tolerance: 12V-10% to 240V+10%
Types E1Z..24-240VAC/DC: 24 to 240V AC/DC
Tolerance: 24V-15% to 240V+10%
Rated consumption: 4VA (1.5W)
Rated frequency: AC 48 to 63Hz
Duty cycle: 100%
Reset time: 100ms
Residual ripple for DC: 10%
Drop-out voltage: >30% of minimum rated supply voltage
Overvoltage category: III (according to IEC 60664-1)
Rated surge voltage: 4kV
6. Output circuit
1 potential free change over contact
Rated voltage: 250V AC
Switching capacity: 2000VA (8A / 250V)
Fusing: 8A fast acting
Mechanical life: 20 x 10
6
operations
Electrical life: 2 x 10
5
operations
at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(according to IEC 947-5-1)
Overvoltage category: III. (according to IEC 60664-1)
Rated surge voltage: 4kV
7. Control input
Input not potential free: terminals A1-B1
Loadable: yes
Max. line length: 10m
Trigger level (sensitivity): automatic adaption to supply voltage
Min. control pulse length: DC 50ms / AC 100ms
8. Accuracy
Base accuracy: ±1% of maximum scale value
Adjusting accuracy: <5% of maximum scale value
Repetition accuracy: <0.5% or ±5ms
Voltage influence: -
Temperature influence: 0.01% / °C
9. Ambient conditions
Ambient temperature: -25 to +55°C (according to IEC 68-1)
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85%
(according to IEC 721-3-3 Klasse 3K3)
Pollution degree: 2, if built-in 3
(according to IEC 664-1)
Vibrations resistance: 10 to 55 Hz 0.35mm
(according to IEC 68-2-6)
Shock resistance: 15g 11ms
(according to IEC 68-2-27)
10. Dimensions
11. Weight
Single packing: 72g
Package 10pcs: 670g per Package
E1ZM, E1Z1
17,5mm
60mm
87mm
44mm5mm
45mm

Summary of content (2 pages)