BAS Integration Manual

© 2015 680_B - 10/15
4 of 8
A Watts Water Technologies Company
Object ID Name Data Type Read / Write Units Range/Value
Binary Input Objects
0 Slab 1 Water BI R No Units (95) 0 = Dry, 1 = Wet
1 Slab 2 Water BI R No Units (95) 0 = Dry, 1 = Wet
2 Combined Water Status BI R No Units (95) 0 = Dry, 1 = Wet
3 System Pump BI R No Units (95) 0 = Off, 1 = On
4 Primary Pump BI R No Units (95) 0 = Off, 1 = On
5 Boiler Pump BI R No Units (95) 0 = Off, 1 = On
6 Boiler Stage 1 BI R No Units (95) 0 = Off, 1 = On
7 Boiler Stage 2 BI R No Units (95) 0 = Off, 1 = On
Binary Value Objects
0
Outdoor Sensor Enable BV R/W
No Units (95)
0 = Control to measure
outdoor air temperature
1 = BAS to send
outdoor air temperature
1
Melt/Stop Request BV R/W
No Units (95)
0 = Off, 1 = Melt
2
Storm/Stop Request BV R/W
No Units (95)
0 = Off, 1 = Storm
3
Idle Enable BV R/W
No Units (95)
0 = Idling disabled,
1 = Idling enabled
4
Storm Enable BV R/W
No Units (95)
0 = Storm disabled,
1 = Storm enabled
5
WWSD Enable BV R/W
No Units (95)
0 = WWSD disabled,
1 = WWSD enabled
6
CWCO Enable BV R/W
No Units (95)
0 = CWCO disabled,
1 = CWCO enabled
Refer to the Installation & Operation Manual 680_D for additional information.
Troubleshooting
If there is no communication, check the following:
Check the ethernet cable. Cable length must not exceed 150 ft. (45 m) for CAT-5E or 300 ft. (90 m) for CAT-6.
If the cable was manually made, check continuity across each of the wires.
If there is intermittent communication, check the following:
Check the ethernet cable. Cable length must not exceed 150 ft. (45 m) for CAT-5E or 300 ft. (90 m) for CAT-6.
BACnet Binary Parameters
Binary Input Object = BI Binary Value Object = BV Read = R Write = W