BAS Integration Manual

Snow Melting Control 680
680
_
B
10/15
Replaces: 04/15
BAS Integration Manual
© 2015 680_B - 10/15
1 of 8
A Watts Water Technologies Company
Snow Melting
Introduction
Table of Contents
BACnet Protocol Implementation Conformance
Statement (PICS) ......................................................... 2
BACnet Connection ...................................................... 2
BACnet Analog Parameters .......................................... 3
BACnet Binary Parameters ........................................... 4
Modbus Specification ................................................... 5
Modbus Connection ...................................................... 5
Modbus Troubleshooting .............................................. 5
Modbus Parameters ..................................................6-7
Error Codes ..................................................................8
The Snow Melting Control 680 can communicate with a Building Automation System (BAS) using either BACnet
®
I P,
BACnet
®
MSTP or Modbus
®
MSTP.
This manual provides information about control parameters that can be accessed by building automation or management
systems that use BACnet or Modbus communication.
1 234
Injection
Mixing
Pmp
46 47
N
Snow Melting Control 680
BAS, Boiler & Mixing
37 38
Mod
Boiler
33 34
Stage 1Stage 2
35 36
+
-
BACnet IP
Signal wiring must be
rated at least 300 V
For product literature:
www.tekmarControls.com
Meets Class B: Canadian
ICES & FCC Part 15
tektra 1070-01
Designed and
assembled in Canada
H7021B
Input Power:
115 V (ac) ±10%, 60 Hz, 320 VA
Primary, System Pump Relays:
230 V (ac), 10 A, 1/2 hp
Boiler Stage Relays:
230 V (ac), 5 A
Injection Mixing Pump:
230 V (ac), 2.4 A
Boiler Pump Relay:
230 V (ac), 5 A, 1/3 hp
Floating Action Mixing Output:
230 V (ac), 5 A
BluBrn /
Slab
25
Blk /
Com
26 27 28
Red
19
Brn /
Slab
20
Blk /
Com
Yel
21
Red
24
Blu
22
Yel
23
Snow / Ice Sensor 1 Snow / Ice Sensor 2
Do Not Apply Power
41 42 43
Pwr
Floating
Action Mixing
ClsOpn
Boiler
39 40
Pump
Pump
29 30
Pump
Primary System
31 32
44 45
Power In
NL
BACnet MSTP
Modbus MSTP
16 17 18
Gnd
BA
RS-485
+–
20V
3
dc
5V
dc
Out
0-10V /
4-20mA In Out
Flow
Sensor
Pressure
Sensor
In
Vdc
6
Gnd
7
mA
45
+
Com
8
Boil
Sup
Out
9
Boil
Ret
10
ComCom
11
Sys
Sup
12
Sys
Ret
13 14 15
+
1
Analog
Mixing
2
Temperature Sensors
+–
Disconnect All Power
Before Opening
Use supply wires suitable for at least 105°C
Employer des fils d’alimentation pour au moins 105°C
Do Not Apply Power

Summary of content (8 pages)