Service Manual

© 2015 680_D - 10/15 38 of 48
Idle Operation
When the snow melting system starts from a cold temperature,
there may be a long time delay before the slab is warm enough
to melt snow. This time delay allows snow to accumulate on
the slab which is not acceptable in some commercial and
institutional applications. To decrease the start-up time, the slab
can be pre-heated to maintain a minimum temperature. This
is known as the Idle temperature. Idling requires large energy
consumption and is generally recommended for institutional
and/or commercial installations where safety concerns are
paramount. The display shows "System is Idling" when the
control is in idle operation.
When designing a snow melting system, an engineer may
specify the amount of allowed snow accumulation as the
Snow-Free Area Ratio. There are three different levels. A
Snow-Free Area Ratio of 1 is defined as a system that melts
all snow as it falls with no allowed accumulation. This requires
that the Idle temperature be set just below freezing. Examples
of these types of applications include:
Hospital emergency areas
Helicopter landing pads
Parking garage ramps
A Snow-Free Area Ratio of 0.5 is defined as a system with
partial snow accumulation on the slab but not in all areas.
These types of systems may also use Idling but usually set
at a temperature several degrees below freezing to reduce
energy consumption. Applications may include:
Steep residential driveways
Commercial sidewalks
Loading docks
A Snow-Free Area Ratio of 0 is defined as a system that
allows snow accumulation. These systems operate the snow
melting system from a cold start resulting in the lowest energy
consumption costs and the longest times to start melting snow.
In this case set the Idle to off. This is recommended for most
residential applications such as:
Flat residential driveways
Patios
Residential sidewalks
Some systems are designed for keeping a slab surface free of
ice rather than free of snow. The most common applications
include:
Car wash bays and aprons
Aircraft hanger aprons
Turf conditioning on golf course greens
These systems require the use of Idling at or near freezing through-
out the winter and may result in high energy consumption.
Storm Operation
For many applications it is too costly to Idle the snow melt system
all winter. The Storm operation combines the benefits of a fast
response time together with lower operating costs. The Storm
operation does this by allowing the user to manually pre-heat
the slab temporarily in preparation of a snowfall warning. In
the event that snow falls and is detected by a Snow/Ice Sensor
or a Snow Sensor or the system is manually started, the snow
melt system heats the slab up to the melting temperature
and completes a melting cycle. Should no snow fall during
the storm time period, the control exits Storm operation and
returns to Off.
The Storm operation is set up by setting the Storm temperature
and the Storm Run Time in the Setpoints menu. The Storm
operation is activated by the Storm/Stop Request parameter
in the BACnet or Modbus communication protocol.
Slab Temperature Control
Controlling the slab temperature is critical to minimizing the
cost of snow melting. This requires that either a Snow/Ice
Sensor 090 or 094 or a Slab Sensor 072 or 073 is installed.
The Snow/Ice Sensor contains a built-in slab temperature
sensor. While the control can operate without a slab sensor
installed, operating costs are much higher.
The slab is operated using slab outdoor reset. As the outdoor
temperature gets colder, the heat loss of the slab increases.
In order to keep the slab surface at a constant temperature
while operating, the inner core of the slab must be heated
above the melt, idle or storm temperature setting. The amount
that the slab inner core temperature is above the melt, idle
or storm setting is proportional to the outdoor temperature.
Since the slab sensor is installed below the surface of the
slab, it is not measuring the true slab surface temperature but
rather the inner core temperature. The control automatically
compensates for this temperature difference. The Slab item in
the Status menu displays the actual measured temperature,
so it is normal to view slab temperatures that exceed the melt,
idle, or storm temperature settings.
Sur
face temperature = 35ϒF
Decreasing Air Temperature
Increasing Slab Core T
emperature
Slab Surface Temperature is Constant
Slab Outdoor ResetSlab Outdoor Reset
Core (sensor)
is warmer