Service Manual
29 of 48 © 2015 680_D - 10/15
Description Range Access
BBMD PORT
Set the BACnet Broadcast Management Device (BBMD) UDP port on the BACnet
network.
Conditions: Available when BAS Type is set to BACnet-IP.
0 to 65535
Default = 47808
Installer
BBMD TIME
Set the BACnet Broadcast Management Device (BBMD) time-to-live in seconds for foreign
device registration on a BACnet network.
Conditions: Available when 1) BAS Type is set to BACnet-IP, and 2) Register Foreign Device is
set to On.
30 to 65535
seconds
Default = 30
seconds
Installer
BBMD IP
Set the BACnet Broadcast Management Device (BBMD) IP address on the BACnet
network.
Conditions: Available when 1) BAS Type is set to BACnet-IP, and 2) Register Foreign Device is
set to On.
000.000.000.000
to
255.255.255.254
Default =
127.127.127.127
Installer
MAC ADDRESS
This is the Media Access Control (MAC) address of this product.
Conditions: Available when BAS Type is set to BACnet-IP.
XX:XX:XX:XX:
XX:XX
Installer
BACnet-MSTP DEVICE ID
Set the BACnet MSTP device identification number. Each device on the BACnet network
must have a unique identification number.
Conditions: Available when BAS Type is set to BACnet-MSTP.
0 to 4194302
Default = 1
Installer
BACnet-MSTP ADDRESS
Set the MSTP address. Each MSTP device must have a unique address.
Conditions: Available when BAS Type is set to BACnet-MSTP.
0 to 127
Default = 1
Installer
BACnet-MSTP BAUD RATE
Select the BACnet-MSTP data communication rate. Higher data rates may restrict cable
length and may require terminating resistors at the end of the RS-485 data bus.
Conditions: Available when BAS Type is set to BACnet-MSTP.
9600, 19k2, 38k4,
57k6, 76k8, 115k
Default = 9600
Installer
MODBUS ADDRESS
Set the Modbus address. Each Modbus device must have a unique address.
Conditions: Available when BAS Type is set to Modbus.
1 to 247
Default = 1
Installer
MODBUS DATA TYPE
Select whether the Modbus network uses RTU or ASCII data frame format.
Conditions: Available when BAS Type is set to Modbus.
RTU or ASCII
Default = RTU
Installer
MODBUS BAUD RATE
Select the Modbus data communication rate. Higher data rates may restrict cable length
and may require terminating resistors at the end of the RS-485 data bus.
Conditions: Available when BAS Type is set to Modbus.
2400, 9600, 19k2,
57k6, 115k
Default = 19k2
Installer
MODBUS PARITY
Select if the Modbus communication frame uses a parity bit.
Conditions: Available when BAS Type is set to Modbus.
None, Even, Odd
Default = Even
Installer
BAS Menu (2 of 2)