Service Manual

11 of 48 © 2015 680_D - 10/15
Control Wiring
A primary pump requiring up to 230 V (ac), 10 A, 1/2 hp can be switched
through terminals 29 and 30. For simplicity in wiring and troubleshooting, a
separate breaker for each pump is recommended.
Connect the power source line wire (L) to terminal 29.
Connect a wire from terminal 30 to the pump L.
Connect a wire from the pump N back to the power source neutral.
Connect the ground wire (G) to one of the ground screws provided in the
wiring chamber.
Wiring the Primary Pump
-------------------------------------------------------------------------------
A system pump requiring up to 230 V (ac), 10 A, 1/2 hp can be switched
through terminals 31 and 32. For simplicity in wiring and troubleshooting, a
separate breaker for each pump is recommended.
Connect the power source line wire (L) to terminal 31.
Connect a wire from terminal 32 to the pump L.
Connect a wire from the pump N back to the power source neutral.
Connect the ground wire (G) to one of the ground screws provided in the
wiring chamber.
Wiring the System Pump
-------------------------------------------------------------------------------
N
G
L
L
NG
Ground
Pump
31 32
System
N
G
L
L
NG
Ground
Pump
29 30
Primary
Snow Sensor
-------------------------------------------------------------------------------------------
Slab Sensor
--------------------------------------------------------------------------------------------
Brn/
Slab
19
Blk/
Com
20
Snow/Ice
Sensor 1
Up to two Snow Sensor 095s can be connected to the control.
If the Snow Sensor 1 input is used:
Connect the black wire to terminal 20.
Connect the blue wire to terminal 21.
Connect the yellow wire to terminal 22.
Connect the red wire to terminal 23.
If the Snow Sensor 2 input is used:
Connect the black wire to terminal 20.
Connect the blue wire to terminal 25.
Connect the yellow wire to terminal 27.
Connect the red wire to terminal 28.
Snow
Sensor
095
Brn/
Slab
19
BluBlk/
Com
20 21
Yel
22
Red
23
Snow/Ice Sensor 1
Snow
Sensor
095
Brn/
Slab
24
BluBlk/
Com
25 26
Yel
27
Red
28
Snow/Ice Sensor 2
Brn/
Slab
24
Blk/
Com
25
Snow/Ice
Sensor 2
A Slab Sensor 072 or 073 can be installed either alone or together with a Snow
Sensor 095.
If the Slab Sensor 1 input is used:
Connect the slab sensor to terminals 19 and 20.
If the Slab Sensor 2 input is used:
Connect the slab sensor to terminals 24 and 25.