Install Instructions

8 of 36
© 2019 tekmar 671
_
D - 08/19
Snow/Ice Sensor
---------------------------------------------------------------------------------------
Snow Sensor
-------------------------------------------------------------------------------------------
Slab Sensor
--------------------------------------------------------------------------------------------
A Snow/Ice Sensor 090 or 094 can be connected to the control. The 090 has
a 65' (20 m) cable and the 094 has a 208' (63 m) cable. The cable may be
extended to a total length of 500' (150 m) using 18 AWG cable. Any junction
boxes must kept dry.
If the Snow/Ice Sensor input is used:
Connect the red wire to terminal 1.
Connect the black wire to terminal 2.
Connect the blue wire to terminal 3.
Connect the yellow wire to terminal 4.
Connect the brown wire to terminal 5.
A Snow Sensor 095 can be connected to the control.
If the Snow Sensor input is used:
Connect the red wire to terminal 1.
Connect the black wire to terminal 2.
Connect the blue wire to terminal 3.
Connect the yellow wire to terminal 4.
A Slab Sensor 072 or 073 can be installed either alone or together with a Snow
Sensor 095.
If the Slab Sensor input is used:
Connect the slab sensor to terminals 2 and 5.
Blu
Yel
Brn/
Blk/
Red
Snow
Sensor
095
Blu
Yel
Brn/
Slab
Blk/
Com
Red
Blu
Yel
Brn/
Blk/
Red