Install Instructions

24 of 36
© 2019 tekmar 671
_
D - 08/19
Toolbox Menu
Description Range Access
ERROR CODE
The current error code is displayed.
Conditions: Always available.
See Error Code
Section
User
Installer
ACCESS LEVEL
Select the access level of the control. This determines which menus and items are available
through the user interface.
Conditions: Always available.`
User or Installer
Default = Installer
User
Installer
TYPE 671
Product information.
SW: J1288 1.0.0
SVN: XXX
Conditions:
Always available.
J1288
Last 3 numbers
indicate software
version
User
Installer
LOAD DEFAULTS
Select “Yes” to reload the factory defaults on the control.
Conditions: Always available.
No, Yes
User
Installer
Description Range Access
MANUAL OVERRIDE
Manually override the normal automatic operation of the control to test the equipment or operate
the system at the maximum temperature limits.
Auto = Normal operation.
Max Heat = Operate hydronic system at maximum heat.
Hand = Manual override of each relay output.
Purge = Hydronic system purge operates pumps to help bleed air from the system.
Auto,
Hand,
Max Heat,
Purge,
Off
User
Installer
SYSTEM PUMP
Manually turn on the system pump during the HAND Manual Override.
Off or On
Default = Off
User
Installer
HEAT RELAY
Manually turn on the heat relay during the HAND Manual Override.
Off or On
Default = Off
User
Installer
BOILER ENABLE
Manually turn on the boiler during the HAND Manual Override.
Off or On
Default = Off
User
Installer
HAND DURATION
Select the amount of time that the HAND Override is in effect before returning to Automatic operation.
0:10 to 72:00
hours
Default = 0:10 hour
User
Installer
MAX HEAT DURATION
Select the amount of time that Max Heat is in effect before returning to Automatic operation.
0:10 to 72:00
hours
Default = 24:00 hour
User
Installer
PURGE DURATION
Select the amount of time that the Purge is in effect before returning to Automatic operation.
0:10 to 72:00
hours
Default = 0:10 hour
User
Installer
Override Menu