tekmarNet Menu
Description Range Access
ADDRESSING
The tekmarNet address of this control. To manually set the address, use the up or down buttons.
Auto,
x:01 to bus x:24,
Installer
AUTO ADDRESS
The tekmarNet address of this control.
Conditions: Addressing is set to Auto
Auto
b:01 to b:24
1:01 to 1:24
2:01 to 2:24
3:01 to 3:24
Installer
MANUAL ADDRESS
The tekmarNet address of this control when manually assigned
Conditions: Addressing is set to Manual
Manual
b:01 to b:24
1:01 to 1:24
2:01 to 2:24
3:01 to 3:24
DEVICE COUNT
Provides a count of all the tekmarNet thermostats, setpoint controls and snow melting controls
on the tekmarNet System.
1 to 24
Installer
SNOW MELT ZONE
Select the snow melting zone that this control operates. Snow zone 1 has the highest priority
while snow zone 12 has the lowest priority.
1 to 12
Installer
TRACK ZONE
Select to track and record the running hours of snow zone 1 and repeat this run time on this
control. This allows snow melting zones without a snow/ice sensor to automatically start.
Off or On
Installer
MELT GROUP
A User Switch or Gateway may be used to manually start melting the zone. Set the Melt
Group number to the corresponding Setpoint Enable number on the User Switch.
1 to 12
Installer
STORM GROUP
A User Switch may be used to manually start storm operation of the snow zone. Set the
Melt Group number to the corresponding Setpoint Enable number on the User Switch.
1 to 12
Installer
PRIORITY
Select the priority of the snow melting system.
Off, Conditional,
Full
Default = Off
Installer
AWAY SCENE
Select if the control should accept or ignore the away command from a tekmarNet system.
Conditions: Always available.
Off or On
Default = On
Installer
TN4 SYSTEM PUMP
Select if the system pump located on the tekmarNet System Control should operate when
the snow melt zone is heating.
Off or On
Installer