System Status Menu
Description Range Access
MANUAL MELT INPUT
When Manual Melt wiring terminal 8 is shorted to common wiring terminal 9, the control is enabled
and enters the melting operation unless prevented by warm weather shut down or cold weather
cut off. When the manual melt input is disconnected, the control completes the melting cycle and
then returns to off, idle or storm operation.
Conditions: Available
Off, Enabled
User
Installer
TEKMARNET
When tekmarNet communication is present, the status shows active. When there is no tekmarNet
communication, the status is off.
Conditions: Available
Off, Active
User
Installer
BOILER
Current status of the Boiler relay.
Conditions: Always available
On or Off
User
Installer
SYSTEM PUMP
Current status of the system loop pump.
Conditions: Always available
On or Off
User
Installer
HEAT RELAY
Current status of the heat relay.
Conditions: Always available
On or Off
User
Installer
Slab Status Screen
Description Range Access
OUTDOOR
Current outdoor air temperature as measured by the outdoor sensor or from the tekmarNet
system. “– – –” is displayed when no outdoor temperature reading is available.
– – –,
-67 to 149°F
(-55.0 to 65.0°C)
User
Installer
SLAB TARGET
The slab target calculated by the control based on outdoor temperature and the melting,
idling, or storm setpoints. “- - -” is displayed when no heat is required.
– – –,
32 to 110°F
(0 to 43.0°C)
User
Installer
SLAB SENSOR
Current slab sensor temperature.
-58 to 167°F
(-50.0 to 75.0°C)
User
Installer
SENSOR WATER STATUS
Current status of snow/ice sensor moisture detector.
DRY or WET
User
Installer