Application Guide

671
_
A - 08/19 16 of 16 © 2019 tekmar
Tel: 1-800-438-3903 • Fax: (250) 984-0815
tekmarControls.com
All specications are subject to change without notice
Specifications
The following are the recommended specifications for the WiFi Snow Melting Control 671.
The control shall have the ability to use a snow/ice sensor in order to automatically detect snow or ice and begin operation
of the system. The system shall continue to run until the sensor is dry or the control is manually stopped.
The control shall have the ability to be manually started with an adjustable running time that counts down and automatically
stops the system.
The control shall not operate the system to provide heat to the snow melting zones when it enters into either a Warm Weather
Shut Down (WWSD) or a Cold Weather Cut Off (CWCO) mode.
The system water temperature shall be based on the outdoor temperature and feedback from sensors located in the snow
melting slabs.
The control shall have two separate access levels to limit the number of adjustments available to various users.
The control shall have a manual override that allows each output to be manually turned on or off.
The control shall continuously monitor its temperature sensors and provide an error message upon a control or sensor failure.
The control shall record and display boiler and pump running hours and minimum and maximum temperatures depending
on the access level that has been selected.
During extended periods of inactivity, the pumps that are operated by the control shall be periodically exercised to prevent
seizure during long idle periods.
This Application Brochure is not intended to provide full installation instructions and safety information. In order to avoid property
damage or injury, please refer to the complete installation manual and product safety information provided with the product.