Application Guide

8 of 20
© 2016 tekmar 670
_
A - 10/16
Shared Boiler and Mixing Valve with Optional Tandem Sensors A670-4 Mechanical
670 Application Settings
Setting Name Value
Application Mode Mixing
Mixing Type Floating
Boiler Type Enable
Optional 654 Application Settings
Setting Name Value
Application Mode 090
A1 = Normally Closed Freeze Protection Aquastat
B1 = Boiler Enable
HX = Heat Exchanger
M1 = Actuating Motor 741
P1 = System Pump
P2 = Heat Exchanger Pump
S1a, S1b = Snow/Ice Sensor 090 or 094
S4 = Outdoor Sensor 070
S5 = Boiler Return Sensor 082
S6 = Mix Supply Sensor 082
V1 = 3-Way Mixing Valve 710 through 714
X1 = Transformer 009
Legend
670
Optional
654
S4
S5
P2 P1
S6
V1
HX
M1
S1a
S1b
A1
Description
The WiFi Snow Melting Control 670 operates a snow melting zone warmed from a heat source that is shared with other loads
in a building. The system uses a mixing valve to regulate the water temperature and a heat exchanger isolates the glycol-
filled snow melting system loop from the water-filled main heating system. The 670 is paired with a Snow Melting Control 654
to provide Tandem Snow/Ice Detection using a Snow/Ice Sensor 090 or 094. Tandem sensors double the detection area to
provide increased reliability and redundancy in case of sensor failure.
The system pump operates continuously when heating the slab during melting/idling/storm operation.
The slab temperature is controlled by adjusting the mixing valve position.
When the mixing valve is open, the heat exchanger pump and the boiler enable are on.
The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.
A normally-closed aquastat protects the heat exchanger from freezing by shutting off power to the system pump.
Either snow/ice sensor will start the melting operation if snow or ice is detected. Both sensors must be dry in order to
stop melting.