Application Guide

12 of 20
© 2016 tekmar 670
_
A - 10/16
Modulating Steam Valve A670-6 Mechanical
Application Settings
Setting Name Value
Application Mode Mixing
Mixing Type 0-10 V or 4-20 mA
Boiler Type Enable
B1 = Boiler Enable
HX = Steam-to-Glycol Heat Exchanger
M1 = Modulating Steam Valve
P1 = System Pump
S1 = Snow/Ice Sensor 090 or 094
S2 = Snow Sensor 095
S3 = Slab Sensor 072 or 073
S4 = Outdoor Sensor 070
S5 = Mix Supply Sensor 082
Legend
670
Snow/Ice Sensor Options
S4
S5
P1
HX
M1
S1
S2
S3
Description
The WiFi Snow Melting Control 670 operates a modulating steam valve and a steam-to-water heat exchanger to heat a glycol-
filled snow melting system.
The system pump operates continuously when heating the slab during melting/idling/storm operation.
The slab temperature is controlled by adjusting the modulating steam valve position.
The boiler relay is closed while the modulating steam valve is open. This provides a signal to fire the steam boiler.
The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.
The system operation is dependent on sensor selection, as listed in the table below.
Sensor options Operation methods
Sensor
Sensor Model(s)
Auto Start/
Auto Stop
Auto Start/
Timed Stop
Manual Start/
Timed Stop
Slab Temperature
Control
S1 Automatic Snow/Ice Sensor 090 or 094
S2 Aerial Snow Sensor 095
S3 Slab Sensor 072 or 073
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073