Application Guide

10 of 20
© 2016 tekmar 670
_
A - 10/16
Shared Boiler and Mixing Injection Pump
A670-5 Mechanical
Application Settings
Setting Name Value
Application Mode Mixing
Mixing Type Injection
Boiler Type Enable
A1 = Normally Closed Freeze Protection Aquastat
B1 = Boiler Enable
HX = Heat Exchanger
P1 = System Pump
P2 = Heat Exchanger Pump
P3 = Variable Speed Injection Mixing Pump
S1 = Snow/Ice Sensor 090 or 094
S2 = Snow Sensor 095
S3 = Slab Sensor 072 or 073
S4 = Outdoor Sensor 070
S5 = Boiler Return Sensor 082
S6 = Mix Supply Sensor 082
V1 = Globe Valve
Legend
Sensor options Operation methods
Sensor
Sensor Model(s)
Auto Start/
Auto Stop
Auto Start/
Timed Stop
Manual Start/
Timed Stop
Slab Temperature
Control
S1 Automatic Snow/Ice Sensor 090 or 094
S2 Aerial Snow Sensor 095
S3 Slab Sensor 072 or 073
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073
670
Snow/Ice Sensor Options
S4
S5
P2 P1
S6
P3
HX
S1
S2
S3
A1
V1
Description
The WiFi Snow Melting Control 670 operates a snow melting zone warmed from a heat source that is shared with other loads in
a building. The system uses a variable speed injection pump to regulate the water temperature and a heat exchanger isolates
the glycol-filled snow melting system loop from the water-filled main heating system.
The system pump operates continuously when heating the slab during melting/idling/storm operation.
The slab temperature is controlled by adjusting the speed of the variable speed injection pump.
When the variable speed injection pump is on, the heat exchanger pump and the boiler enable are on.
The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.
A normally-closed aquastat protects the heat exchanger from freezing by shutting off power to the system pump.
The system operation is dependent on sensor selection, as listed in the table below.