Application Brochure

© 2009 A 664 - 12/09 8 of 12
Concept Drawing
This is only a concept drawing, not an engineered drawing. It is not intended to
describe a complete system, nor any particular system. It is up to the system
designer to determine the necessary components for and configuration of the
particular system being designed, including additional equipment, isolation
relays (for loads greater than the control’s specified output ratings), and any
safety devices which in the judgement of the designer are appropriate, in order
to properly size, configure and design that system and to ensure compliance
with building and safety code requirements.
tekmar Control Systems Ltd., Canada; tekmar Control Systems, Inc., U.S.A.; www.tekmarcontrols.com
Head Office: 4611-23rd Street, Vernon, B.C. Canada, V1T 4K7; (250) 545-7749 Fax (250) 545-0650
- Application
Mechanical
A 664-4
12/09
see Essay E 021
Outdoor
Sensor (S6) 070
120 V (ac)
V1
P3
P4
P2 P1
D1
Mix Return
Sensor (S3) 082
Mix Supply
Sensor
(S2) 082
Boiler Supply
Sensor (S1)
082
Slab Sensor
(S4)
072/073
Snow/Ice
Sensor
(S5) 090
664
D1 = External Melt / Idle Demand
P1 = Primary Pump
P2 = Variable Speed Injection Pump
P3 = Zone 1 Pump
P4 = Zone 2 Pump
S1 = Boiler Supply Sensor 082
S2 = Mix Supply Sensor 082
S3 = Mix Return Sensor
S4 = Slab Sensor 072/073
S5 = Snow / Ice Sensor 090
S6 = Outdoor Sensor 070
V1 = Balancing Valve or Globe Valve
System Operation
The Snow Detector & Melting Control 664 provides snow melting for a two zone system. The 664 operates the boiler
based on the current load on the system in order to provide the required mixed supply fluid temperature that satisfies the
load while protecting the slab from thermal stress. The output of the variable speed injection pump (P2) is controlled in
order to protect the boiler from flue gas condensation.