Application Brochure
11 of 12 © 2009 A 664 - 12/09
Concept Drawing
This is only a concept drawing, not an engineered drawing. It is not intended to
describe a complete system, nor any particular system. It is up to the system
designer to determine the necessary components for and configuration of the
particular system being designed, including additional equipment, isolation
relays (for loads greater than the control’s specified output ratings), and any
safety devices which in the judgement of the designer are appropriate, in order
to properly size, configure and design that system and to ensure compliance
with building and safety code requirements.
tekmar Control Systems Ltd., Canada; tekmar Control Systems, Inc., U.S.A.; www.tekmarcontrols.com
Head Office: 4611-23rd Street, Vernon, B.C. Canada, V1T 4K7; (250) 545-7749 Fax (250) 545-0650
- Application
Electrical
A 664-5
12/09
P1P2
Z2Z1
D1
S3
S2S4
S5 S1
S6
Boiler
#2
Boiler
#1
24 V (ac)
Class 2
Transformer
120 V (ac)
L
C
R
N
MM
D2
Opn/
Var
Pwr
Mix
Cls
4-20 mA
+-
Red Blu Yel
Com tN2 Com Boil Out
Blk/
Com
Slab
2
Mix
Ret
Mix
Sup
Zn
1
Zn
2
Sys
P1
Com
Zn
Brn/
Slab1
Melt/Idle
Demand
Stage
1
Stage
2
Power
LN
12345 6789101112131415161718 192021222324252627 29 30
5A5A2.4A 5A 5A 5A
Do not apply power
664
1 kΩ max
28
1
Com
C
2
Opn
3
Cls
C1
Essential Control Settings
ZONE 1 = AUTO
ZONE 2 = AUTO
MIXING = FLOT
Boil SENS = SUP
STAGE 1 = AUTO
STAGE 2 = AUTO
C1 = Actuating Motor 741
D1 = External Melt / Idle Demand
D2 = Remote Start / Stop Module 039
P1 = Primary Pump
P2 = System Pump
S1 = Boiler Supply Sensor 082
S2 = Mix Supply Sensor 082
S3 = Mix Return Sensor 082
S4, S5 = Slab Sensor 072/073
S6 = Outdoor Sensor 070
V1 = 4-Way Mixing Valve
Z1 = Zone 1 Valve
Z2 = Zone 2 Valve