Installation and Operation Manual

© 2013 654_D - 06/13 12 of 44
View Menu (1 of 2)
The View menu items display the current operating temperatures and status information of the system.
Item Field Range Access Description Set to
1 to 12
User
Installer
SNOW ZONE
The snow melt zone number on the tekmarNet
®
system.
Conditions: tekmarNet
®
communication available.
– – –, -76 to
149°F
(-60 to 65°C)
User
Installer
OUTDOOR
Current outdoor air temperature as measured by the local
or remote outdoor sensor. The outdoor air temperature is
shared to all devices in the tekmarNet
®
system. “– – –” is
displayed when no outdoor sensor is available.
Conditions: Application Mode is set to PWM, Boil, Mix or
Elec.
– – –, -76 to
149°F
(-60 to 65°C)
Installer
SLAB TARGET
The calculated slab target of the snow melting system.
“– – –” is displayed when the snow melt control is off.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.
-76 to 149°F
(-60 to 65°C)
User
Installer
SLAB
Current slab temperature as measured by the control.
Conditions: Application Mode is set to PWM, Boil, Mix or Elec
and a snow/ice sensor or slab sensor is installed.
DRY or WET
User
Installer
WATER SENSOR
Current status of the water detection sensor.
Conditions: A snow/ice sensor or snow sensor is installed.
---, 70 to 200°F
(21.0 to 93.5°C)
Installer
BOILER TARGET
The calculated boiler target of the snow melt system.
“– – –” is displayed when the snow melt control is not operating
the boiler.
Conditions: Application Mode is set to Boil.
---, 70 to 200°F
(21.0 to 93.5°C)
Installer
MIX TARGET
The calculated mix target of the snow melt system. “––”
is displayed when the snow melt control is not operating the
mixing valve or mixing injection pump.
Conditions: Application Mode is set to Mix.
-58 to 212°F
(50.0 to 100.5°C)
Installer
SUPPLY
Current system supply temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix.
-58 to 212°F
(50.0 to 100.5°C)
Installer
BOILER RETURN
Current boiler return temperature as measured by the
control.
Conditions: Application Mode is set to PWM, Boil or Mix and
Out/Bret Sensor is set to Bret (boiler return sensor).
0 to 100% Installer
MIX RATE
Current position of the mixing valve or mixing injection
pump speed.
Conditions: Application Mode is set to Mix.
0 to 100% Installer
BOILER RATE
Current firing rate of the modulating boiler.
Conditions: Application Mode is set to Boil and Boiler Type
is set to Mod (modulating boiler).