Application Brochure
© 2013 654_A - 06/13 4 of 16
Single Zone with Boiler and Tandem Snow / Ice Sensors A654-2 Mechanical
Description
A single zone includes two Snow / Ice Sensors 090 or 094 for Tandem Snow / Ice Detection for a wider snow or ice
detection area and backup should one of the two sensors fail. When snow or ice is detected the snow melting system is
automatically started and stops when the slab is dry. Each sensor requires a Snow Melting Control 654. The master Snow
Melting Control 654 operates a hydronic snow melting system using a modulating boiler and a system pump. The boiler
is piped in primary-secondary to the snow melt system to allow the system pump to operate continuously during melting
or idling while allowing the boiler and boiler pump to turn on and off as required. The boiler firing rate is modulated using
a 0-10 V (dc) or 4-20 mA signal. The member Snow Melting Control monitors the Snow / Ice Sensor and relays the sensor
information to the master control using tekmarNet
®
communication.
Outdoor
Sensor 070
Relay 003 Relay 003
Boiler
Supply
Sensor
082
System
Pump
Modulating Boiler
Snow / Ice
Sensor 090
or 094
654
Master
654
Member
Snow / Ice Sensor
090 or 094
654 Master - Application Settings
Setting Name Value
APP MODE BOIL
BOIL TYPE MOD (modulating boiler)
AUX RELAY SYS (system pump)
Recommended Accessories
Qty Part Name Part Number
2 Relay 003
1 Transformer 009
Snow or Ice Detector
Option
Start and Stop Sequence
Sensors Required (sold separately)
1 Auto start / Auto stop Snow / Ice Sensor 090 or 094
654 Member - Application Settings
Setting Name Value
APP MODE 090