Install Instructions

25
The Heat On symbol is shown on the display when the thermostat is heating.
Heating for freeze protection is provided whenever the air or floor temperature falls below 40
°
F (4.5
°
C),
regardless of operating mode.
The Cool On symbol is shown on the display when the thermostat is cooling.
The thermostat supports two heating system types: 1) conventional, or 2) heat pump.
Conventional Systems
A conventional heating system includes: furnaces, air conditioners, hydronic heating systems with
baseboards, radiant floors, or fan coils and electric heating.
The thermostat supports up to two heating stages, two cooling stages, a fan and two accessory relays.
EQUIPMENT SETTING 1H/1C 1H/2C 2H/1C 2H/2C
First stage heating W1 W1 W1
W1
Second stage heating - - W2
W2
First stage cooling Y1 Y1 Y1
Y1
Second stage cooling - Y2 -
Y2
Fan G
Accessory 1 Choice of: Humidifier, Dehumidifier, HRV/ERV
Accessory 2 Choice of: Humidifier, Dehumidifier
Heat Pump Systems
A heat pump system may include additional heat sources as backup. The thermostat supports up to
four heating stages, two cooling stages, a reversing valve, a fan and one accessory relay.
EQUIPMENT SETTING 1HP 1HP/1AUX 1HP/2AUX 2HP 2HP/1AUX 2HP/2AUX
First stage heating Y1 Y1 Y1 Y1 Y1 Y1
Second stage heating - W1 W1 Y2 Y2 Y2
Third stage heating - - W2 - W1 W1
Fourth stage heating - - - - - W2
First stage cooling Y1 Y1 Y1 Y1 Y1 Y1
Second stage cooling - - - Y2 Y2 Y2
Fan G
Accessory 1 Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator
Accessory 2 Reversing valve O relay remains closed during cooling.
Reversing valve B relay remains closed during heating.
Heating and Cooling Operation
Sequence of Operation