Setting Range Default
ROOM HOT WARNING
Error on home screen if the room exceeds this temperature.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
ROOM COLD WARNING
Error on home screen if the room falls below this tempera-
ture.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
LOW HUMIDITY WARNING
Error on home screen if the humidity falls below this thresh-
old.
Off, 5 to 95% Off
HIGH HUMIDITY WARNING
Error on home screen if the humidity exceeds this threshold.
Off, 5 to 95% Off
AUXILIARY HEAT RUN TIME WARNING
Error on home screen if the auxiliary heat W1 or W2 runs
continuously for longer than this setting. This setting
only applies for heat pump systems.
Off, 1 to 24 hours Off
AIR FILTER CHANGE WARNING
Error on home screen to change the air filter when the fan
exceeds this run time.
Off, 200 to
2000 hours
Off
UV LAMP CHANGE WARNING
Error on home screen to change the UV disinfectant lamp
when it exceeds this run time.
Off, 10,000 to
50,000 hours
Off
Setup - Alerts