Install Instructions

17
Setting Range Default
Screen Page 1
FLOOR MIN:
Select the floor temperature minimum. Applies when there
is both floor and an air sensors and when no schedule is set.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
HEAT TO AWAY
Select the heating temperature when away.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
62°F
16.5°C
HEAT TO MIN LIMIT
Select the minimum heating temperature limit.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
HEAT TO MAX LIMIT
Select the maximum heating temperature limit.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
COOL TO AWAY
Select the cooling temperature when away.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
COOL TO MIN LIMIT
Select the minimum cooling temperature limit.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
COOL TO MAX LIMIT
Select the maximum cooling temperature limit.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
Screen Page 2
FLOOR MIN - WAKE
Select the floor temperature while in the wake schedule.
Applies when there is both a floor and an air sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
FLOOR MIN - LEAVE
Select the floor temperature while in the leave schedule.
Applies when there is both a floor and an air sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
FLOOR MIN - RETURN
Select the floor temperature while in the return schedule.
Applies when there is both a floor and an air sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
FLOOR MIN - SLEEP
Select the floor temperature while in the sleep schedule.
Applies when there is both a floor and an air sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
FLOOR MIN - AWAY
Select the floor temperature while in away.
Applies when there is both a floor and an air sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
Screen Page 3
FLOOR MAX
Select the maximum floor temperature. This protects the
floor covering from over heating. Applies when there is a
floor sensor.
Off, 40 to 95°F
Off, 4.5 to 35.0°C
Off
WARM WEATHER SHUT DOWN
Select the outdoor temperature at which the heating is shut off.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
COLD WEATHER SHUT DOWN
Select the outdoor temperature at which the cooling is shut off.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
HEAT PUMP BALANCE POINT
Select the outdoor temperature at which the heat pump is
shut off and the backup heat source is operated exclusively.
Off, 10 to 70°F
Off, -12.0 to 21.0°C
Off
Setup - Temp