Installation and Operation Manual
© 2012 557_D - 11/12
11 of 48
A Watts Water Technologies Company
Setting Display
COOL MAXIMUM ROOM LIMIT
Set the maximum room cooling limit.
Access Level: Installer
Range: 50 to 100°F (10.0 to
38.0°C)
Conditions: Always available Default: 100°F (38.0°C)
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1 or HRF2.
Default: 72°F (22.0°C)
FLOOR MINIMUM
Set the floor heating temperature while in the
event.
Access Level: Installer, User
Range: OFF, 40 to 122°F (4.5 to
50.0°C)
Conditions: Sensor 1, 2 or 3 is set to Floor, and W1
Terminal is set to HRF1 or HRF2, & Schedules are
in use or Scenes are set to All or Guest.
Default: OFF
FLOOR MAXIMUM
Set the floor maximum temperature in order to
protect the floor covering.
Suggested settings: Tile = 90°F (32°C)
Hardwood Floor = 85°F (29°C)
Access Level: Installer
Range: 40 to 122°F (4.5 to
50.0°C), OFF
Conditions: Sensor 1, 2 or 3 is set to Floor, & W1
Terminal is set to HRF1 or HRF2.
Default: 85°F (29.5°C)
TEMPORARY HOLD
Temperature adjustment in the home menu
can result in either permanent temperature
setting change or temporary temperature setting
change that lasts 3, 6, 9, 12 hours or until the
next scheduled event.
Access Level: Installer Range: OFF or ON
Conditions: None Default: OFF
Set Temp Menu (3 of 4)