Install Instructions
© 2012 557_D - 08/12
31 of 48
A Watts Water Technologies Company
Heating Operation
Section A
Sequence of Operation
Set Heat Temperature
-----------------------------------------------
-----------------------------------------------
The 557 can operate radiant floor heating, heat pump stage 1 and stage 2, and a backup
heat source to provide heating in different combinations depending on the outdoor air
temperature. The illustration below shows when each of the available heating units are
available. The “Heat On” symbol is shown on the display when the thermostat is heating. If not
operating a heat pump, the first and second stage of heat (W1 and W2) are allowed to turn
on below the Warm Weather Shut Down to maintain the Set Heat Room temperature.
No heating Air heating only All allowedNo backup heat
Colder
Outdoor
Temperature
Set Heat
Room
Room
Warmer
Room
Colder
Warm Weather
Shut Down
Default = 70°F
Radiant Floor
Warm Weather
Shut Down
Default = 60°F
Balance
Point
Default = Off
Lockout
Default = 60°F
Heat Pump - Heating Mode
No heat pump
Y2 off
Y1 off
Y2 on
Y1 on
W2 off
Y2 off
Y1 off
W1 off
W2 on
Y2 on
Y1 on
W1 on
Y2 off
Y1 off
W1 off
Y2 on
Y1 on
W1 on
W2 off
W1 off
W2 on
W1 on
Air Temperature Heating
---------------------------------------------
---------------------------------------------
When using only a room temperature sensor, the thermostat operates the heating
system to maintain the Set Heat Room temperature.
Floor Heating
--------------------------------------------------------
--------------------------------------------------------
When using both a room and a floor temperature sensor, the thermostat always maintains
the Floor Minimum temperature, even when the air temperature is satisfied. When the
air temperature is below the Set Heat Room temperature, the thermostat operates the
heating system to maintain the Set Heat Room temperature. The floor is never heated
above the Floor Maximum setting in order to protect the floor covering. Suggested
Floor Maximum settings are 90°F (32°C) for tile, stone, or concrete floors and 85°F
(29°C) for wood floors.
Radiant Floor Baseload
----------------------------------------------
----------------------------------------------
When the terminal unit is selected to be a Hydronic Radiant Floor (HRF1 or HRF2)
and no floor temperature sensor is installed, the thermostat has option to provide
baseload heating. This allows the radiant floor to be heated even though the room air
temperature is satisfied. This is useful in areas where a radiant floor heating zone is
overlapped by an air heating system. The radiant floor heating is overwhelmed by the
quick heat up rate of the air heating system, resulting in a radiant floor heating zone
that rarely turns on. The radiant baseload option allows the radiant floor to counteract
the air heating system by heating the floor at a reduced output even when the room air
temperature is satisfied. This is also useful in areas that experience large solar gains
through windows. The radiant baseload is automatically shut off in the summer by the
warm weather shut down feature.










