Toolbox Menu (3 of 3)
Setting Display
DEVICE COUNT
Provides a count of all the tekmarNet
®
thermostats
and setpoint controls on the tekmarNet
®
system.
Access Level: Installer
Range: 1 to 24
Conditions: Must be connected to a tekmarNet
®
system.
Default: 1
USER TEST
Use the up or down arrow keys to select either the
heat or cool test sequence, then press the NEXT key
to begin. Press HOLD to pause at step for 5 minutes.
Press NEXT to advance to the next step.
Access Level: Installer
Range: OFF, HEAT or COOL
Conditions: Always available.
Default: OFF
OFFSET ROOM
Manual offset correction of the room temperature
measurement.
Access Level: Installer
Range: -5 to +5°F (-3.0 to +3.0°C)
Conditions: Always available.
Default: 0°F (0.0°C)
OFFSET HUMIDITY
Manual offset correction of the room humidity
measurement.
Access Level: Installer
Range: -10 to +10%
Conditions: Always available.
Default: 0%
FILTER CHANGE HOURS
Select the amount of time the fan operates before
the air filter requires maintenance.
Access Level: Installer Range: OFF, 200 to 2000 hours
Conditions: Always available. Default: OFF
LOAD FACTORY DEFAULTS
Touch Enter to load the factory defaults settings.
Access Level: Installer Range: None
Conditions: Always available. Default: Keep existing settings
ERROR HISTORY 1 THROUGH 5
Displays a history of the last 5 errors that have occurred
on the thermostat in the past 30 days. Touch Enter
to manually clear the error code.
Access Level: Installer
Range: See Troubleshooting
section
Conditions: An error must have occurred.
Default: Not applicable