Install Instructions

© 2015 554_D - 02/15
40 of 44
A Watts Water Technologies Company
Error Message Description
DISPLAY MENU SAVE ERROR
The thermostat failed to read the Display menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error.
To clear the error, set the access level to Installer and check all settings
in the Display menu.
tN2 PORT ERROR
The thermostat has been connected to a tN2 zone already in use by a
2-stage thermostat. This error may also occur if 24 V (ac) is incorrectly
wired to the tN2 wiring terminals.
To clear the error, move the thermostat’s tN2 wires to an unused tN2
port on the zoning control or check the tN2 wires for 24 V (ac).
tekmarNet
®
COMMUNICATION ERROR
The tekmarNet
®
communication bus has either an open or a short
circuit. The result is that there are no communications. Check for loose
wires between tN4 and C. Check for short circuits between the tN4
and C wires on the House Control, Wiring Center, or Zone Manager.
Check for correct polarity between the C and R wires.
The error clears automatically once the wiring fault has been
corrected.
To force the error to clear while allowing a short or open circuit to
continue, touch the Cancel key.
ADDRESS ERROR
Two thermostats have been manually set to the same address. The
thermostat continues to operate with this error but does not communicate
with the tekmarNet
®
system.
To clear this error, select an unused tekmarNet
®
address or select
automatic addressing.
DEVICE LIMIT
More than 24 devices (thermostats or setpoint controls) have been
connected to the tekmarNet
®
communication bus. To clear the error,
remove and relocate devices to other available buses until the device
count is 24 or less.
ROOM SENSOR SHORT CIRCUIT ERROR
Due to a short circuit, the thermostat is unable to read the built-in room
temperature sensor. If Sensor 1 or 2 is set to Room, or the thermostat
is connected to a tekmarNet
®
system control, the thermostat continues
to operate; otherwise operation stops.
The error cannot be field repaired. Contact your tekmar
®
sales
representative for repair procedures.
Error Messages (2 of 4)