Install Instructions
© 2015 554_D - 02/15
32 of 44
A Watts Water Technologies Company
Fan Operation
The fan operates together with the air heating or cooling systems. The user can also
select to operate the fan manually by pressing the Fan button. This allows the user to
choose between Auto and On. “Auto” allows the fan to operate with heating or cooling,
but normally the fan is off. “On” forces the fan to operate continuously.
Ventilation Fan
------------------------------------------------------
In order to provide ventilation to a building, the fan can operate beyond the time required
for the heating and cooling systems. Vent Mode allows the user to set the fan to operate
for 10 to 90% of an hour, in 10% (6 minutes per hour) increments, as well as in Auto
and On mode. This is available when the Vent Mode setting in the Setup menu is set
to On.
Once Ventilation is set to On, the Fan minimum run time percentage during the and
events can be set so that the fan can operate on a schedule and/or together with scenes.
Fan Post Purge
------------------------------------------------------
The fan relay includes a post purge feature that operates the fan after the heating or
cooling system has shut off. When a duct temperature sensor is installed the length
of post purge is based on the air duct temperature and the Heat Purge or Cool Purge
temperature settings. When there is no duct temperature sensor installed, the length
of post purge is based upon the Heat Purge and Cool Purge time settings.
Hydronic System Supply Pump
---------------------------------------
When connected to a tekmarNet
®
system control, the thermostat’s W Pump setting
affects the operation of the primary pump or mix pump on the system control. When
the thermostat is connected to the boiler bus, the boiler system or primary pump is
operated. When the thermostat is connected to the mix bus, the mix system pump is
operated.
If the thermostat operates a motorized or thermal motor zone valve, the W Pump setting
should be set to On.
If the thermostat operates a thermal motor (wax actuator) zone valve, set the W Thermal
Motor setting to On. This provides a three-minute delay to allow the zone valve to open
before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the W Pump setting can be set
to Off. This allows a Zone Group Pump located on the Zone Manager, or Wiring Center
to operate the pump for the manifold.
DHW Tank Priority
---------------------------------------------------
When a tekmarNet system control is heating an indirect Domestic Hot Water (DHW) tank,
the thermostat may shut off the heating zones to allow the DHW tank to recover quickly.
Priority is determined by the DHW priority setting on the tekmarNet system control.










