Setup Menu (4 of 4)
Setting Display
FAN DELAY
Select the time delay to allow the fan coil or furnace
to warm up prior to activating the fan. This avoids
blowing cold air.
Access Level: Installer
Range: NONE, 0:10 to 6:00
minutes
Conditions: Sensor 1 is not set to COIL and W
TERMINAL is set to COIL or FURN.
Default: 0:30 minutes
HEAT COIL MINIMUM
Select the minimum coil temperature before operating
the fan for heating.
Access Level: Installer
Range: OFF, 70 to 180°F
(OFF, 21.0 to 82.0°C)
Conditions: Sensor 1 is set to COIL and W TERMINAL
is set to COIL.
Default: 110°F (43.5°C)