Install Instructions
© 2015 554_D - 02/15
26 of 44
A Watts Water Technologies Company
Setup Menu (1 of 4)
Setting Display
SENSOR 1
Select the auxiliary sensor input 1 type.
Access Level: Installer
Range: OFF, ROOM, FLOR (floor),
COIL, DUCT
Conditions: Coil sensor option available when W
TERMINAL is set to COIL.
Duct sensor option available when W TERMINAL is
set to FURN or COIL.
Floor sensor option not available when W TERMINAL
is set to FURN or COIL.
Default: OFF
SENSOR 2
Select the auxiliary sensor input 2 type.
Access Level: Installer
Range: OFF, ROOM, FLOR (floor),
OUT (outdoor)
Conditions: Floor sensor option not available when
W TERMINAL is set to FURN or COIL.
Default: OFF
ROOM SENSOR
Select whether the built-in room temperature sensor
is on or off.
Access Level: Installer Range: OFF or ON
Conditions: Only available when Sensor 1 or 2 is
set to ROOM.
Default: ON
W TERMINAL UNIT
Select the heating equipment the W relay operates.
HRF1 & 2 = High & low mass hydronic radiant floor
CONV = Baseboard convectors
COIL = Fan coil
FURN = Furnace
OTHR = Other than hydronic heating
Access Level: Installer
Range: HRF1, HRF2, CONV,
COIL, FURN, OTHR
Conditions: HRF1, HRF2, CONV, COIL only available
when connected to a tekmarNet
®
System Control.
Default:
OTHR (standalone)
HRF1 (tekmarNet
®
System Control)
W PUMP
Select whether the primary or mix system pump on
a tekmarNet
®
system control should operate while
the first stage of heat W is operating.
Access Level: Installer Range: OFF or ON
Conditions: Available when a tekmarNet
®
system control
is connected and W TERMINAL is set to HRF1, HRF2,
CONV or COIL. Also available when connected to a
tN2 Wiring Center and W TERMINAL set to OTHR.
Default: ON