Install Instructions

© 2015 554_D - 02/15
15 of 44
A Watts Water Technologies Company
Setting Display
FAN
Set the minimum percentage of time the fan should
operate while in the event. This provides ventilation
for the building. Each 10% is 6 minutes per hour.
Access Level: Installer, User Range: Auto, 10 to 90%, ON
Conditions: 10 to 90% available if Ventilation Mode is
On.
Default: Auto
FAN
Set the minimum percentage of time the fan should
operate while in the event or Away scene. This
provides ventilation for the building. Each 10% is 6
minutes per hour.
Access Level: Installer, User Range: Auto, 10 to 90%, ON
Conditions: Schedules used or Scenes set to Guest or
All.
10 to 90% available if Ventilation Mode is On.
Default: Auto
Set Temp Menu (4 of 4)