Submittal Sheet
Job __________________________
Designer ______________________
Contact _______________________
tekmarNet
®
Thermostat 553
553
_
C
04/13
Zoning
Replaces: New
Submittal
© 2013 553_C - 04/13
1 of 2
A Watts Water Technologies Company
Energy Saving Features
------------
------------
Programmable Schedule
Zone Synchronization
Zone Post Purge
Warm Weather Shut Down
Cooling Interlock
Auto Heating Cycle
Temporary Hold
Away Scene Key
Additional Features
----------------
----------------
2 Auxiliary Sensor Inputs
tekmarNet
®
Communication Compatible
Touchscreen Technology
Outdoor & Floor Temperature Display
Backlight
Radiant Floor Heating & Cooling
Freeze Protection
Pump & Valve Exercising
Heat / Cool Priority
Air Group Master or Member
Network Schedule Master or Member
Optimum Start
Scenes
Daylight Savings Time
Room Temperature Limiting
Relative Humidity Control
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Specifications
-----------------------------------------------------
-----------------------------------------------------
The tekmarNet
®
Thermostat 553 is a communicating touchscreen thermostat designed to operate two heating stages, one cooling
stage, a fan and relative humidity. The heating stages can be hydronic, forced air or a single stage heat pump. The cooling stage is
either an air conditioner or heat pump. There are two auxiliary sensor inputs available to measure room, floor, outdoor, coil or duct
temperature. The optional floor sensor allows precise heating of radiant floors by controlling the floor temperature and maintaining the
desired room air temperature. Relative humidity level can be measured and controlled using the built-in humidity sensor. The large
touchscreen allows you to easily adjust 7-day programmable schedules and room temperature to optimize comfort and energy savings.
The 553 can connect to tekmarNet
®
controls using two or four wires or it can operate as a stand-alone device.
SPECIAL REQUIREMENTS
This thermostat is designed to be used with a tekmarNet
®
House Control, Wiring Center or Zone Manager for power and communication.
It can also be used in stand alone applications.
tekmarNet
®
Thermostat 553 Two Stage Heat, One Stage Cool, Fan
Literature 553_A, 553_C, 553_D, 553_Q, 553_U
Control Microprocessor control. This is not a safety (limit) control
Packaged weight 0.8 lb. (350 g)
Dimensions 5” H x 3-1/4” W x 15/16” D (127 x 82 x 23 mm)
Enclosure White PVC plastic, NEMA type 1
Approvals
Meets Class B: ICES & FCC Part 15
Ambient conditions
Indoor use only, 32 to 122°F (0 to 50°C),
RH ≤90% non-condensing
Environmental
Compatible with chlorinated swimming pool environments.
Do not use in presence of ammonia (animal barns), methanol,
ethanol, acetone.
Power supply 24 V ±10%, 60 Hz, 1.8 VA standby, NEC / CEC Class 2
Relays 24 V (ac) 2 A
Humidity sensor 0 to 90% ± 3% RH
Temperature sensor
NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included None
–Optional
tekmar type # 070, 071, 072, 073, 076, 077, 079, 082, 083, 084
Warranty Limited 3 Year (See 553_D for full warranty)
Side ViewFront View
5”
(127 mm)
3-1/4”
(82 mm)
15/16”
(23 mm)
Mounting Base
C
tN2
tN4
tN2
R
Rh W Rc Y G/O S1 S2
ACC Com
No Power
1-1/2”
(38 mm)
9/16”
(14 mm)
CL
1-7/8”
(47 mm)
3/4”
(19 mm)
CL
CL
13/16”
(20 mm)
4”
(102 mm)
2-1/2”
(64 mm)
29/32”
(23 mm)
3-1/4”
(83 mm)