553_D 04/13 tekmarNet® Thermostat 553 Zoning Replaces: New Installation & Operation Manual Introduction The tekmarNet® Thermostat 553 is a communicating touchscreen thermostat designed to operate one or two heating stages, one cooling stage, a fan and relative humidity.
Table of Contents Getting Started ...............................2 Installation ...........................................3 Caution............................................3 Preparation .....................................3 Removing The Thermostat Base ....3 Mounting The Thermostat Base .....4 Thermostat Wiring ..........................4 Compatible Sensors .......................5 Testing the Thermostat Wiring ........5 Mounting the Thermostat ................6 Switch Settings ........................
Installation Caution Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury or death. It is your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed into the control circuit.
Mounting The Thermostat Base If a single gang box is used: • Feed the wiring through the large hole of the thermostat base. • Fasten the base of the thermostat to the gang box. • Terminate wiring to the wiring strip. • Push the thermostat front onto the thermostat base. If a gang box is not used: • Feed the wiring through the large hole in the thermostat base. • Mount the thermostat base directly to the wall. • Use screws in the screw holes to fasten the thermostat to the wall.
Compatible Sensors The thermostat is compatible with Indoor Sensor type 076, 077, 084, Slab Sensor type 072, 073, 079, Outdoor Sensor type 070, Universal Sensor 082 and Duct Sensor type 083. Testing the Thermostat Wiring Testing tekmarNet ® 2 Wiring ---------------------------------------------------------------Testing the Power If the thermostat display turns on, this indicates that the thermostat is operating correctly and there are no electrical issues.
User Test Sequence Heat Test Step Cool Test Relay(s) Closed Step Relay(s) Closed O RELAY ON Rc to G/O O RELAY OFF Rc to G/O B RELAY OFF Rc to G/O B RELAY ON Rc to G/O FAN ON Rc to G/O (conventional) Rc to ACC (heat pump) FAN ON Rc to G/O (conventional) Rc to ACC (heat pump) Y HEAT ON Rc to Y Y COOL ON Rc to Y W2 HEAT ON Rc to ACC HUMIDIFY ON Rc to ACC W HEAT Rh to W DEHUMIDIFY ON Rc to ACC HUMIDIFY ON Rc to ACC (heat and cool) Rc to Y (two-stage heat) HRV ON Rc to ACC DEHUMI
Lock Switch Settings Switch Settings 1 2 Unlock Unused Back of Thermostat ON Mmm YYYY Lot # 12345 / tekmarNet Thermostat 553 Two Stage Heat, One Stage Cool, Fan www.tekmarcontrols.com Power: tN2 or 24 V (ac) ±10% 1.8 VA Relay: 24 V (ac) 2 A Designed and assembled in Canada Meets Class B: ICES & FCC Part 15 Switch Position Action ON LOCK ACCESS LEVEL Thermostat is locally locked and the access level cannot be changed. Set to Lock when installation has been completed.
User Interface Home Screen Display Humidity, Heat Cool settings, Floor or Outdoor temperature Adjust the Time Adjust the Schedule Room Temperature Away Key Turn the Fan on Switch between Auto, Heat, Cool, Off & Emergency Mode Adjust the Temperature Home Button Return to the ‘Home’ Screen from any menu Symbols Description HEAT ON Heat is turned on. WARNING SYMBOL Indicates an error is present. COOL ON Cooling is turned on. ARROWS Adjust the displayed setting. FAN The fan is turned on.
Programmable Settings Programming Menus Press and hold the Home button for 3 seconds to enter the programming menus. The thermostat returns to the last programming menu previously used. Press and hold for 3 seconds to access the programming menus. Select a Programming Menu --------------------------------------------------------------• Touch “NEXT” to advance (clockwise in above illustration) to the next menu. • Touch “BACK” to go backwards (counterclockwise in above illustration) through the menus.
Set Temp Menu (1 of 4) Setting Display SET HEAT ROOM Set the room heating temperature for the Room event. Access Level: Installer, User Range: 40 to 95°F (4.5 to 35.0°C) Conditions: Always available. Default: 70°F (21.0°C) SET HEAT ROOM Set the room heating temperature for the Room event. Access Level: Installer, User Conditions: Schedules are in use or Scenes are set to All or Guest. Range: 40 to 95°F (4.5 to 35.0°C) Default: 65°F (18.
Set Temp Menu (2 of 4) Setting Display SET HEAT FLOOR Set the floor heating temperature for the event. Access Level: Installer, User Conditions: Room Sensor set to OFF and Sensor 1 or Sensor 2 set to Floor and Schedules are in use or Scenes are set to All or Guest. Floor Range: 40 to 95°F (4.5 to 35.0°C) Default: 65°F (18.5°C) WARM WEATHER SHUT DOWN Set the outdoor air temperature at which heating is suspended during the event. Access Level: Installer Conditions: An outdoor sensor must be available.
Set Temp Menu (3 of 4) Setting Display COOL MINIMUM ROOM LIMIT Set the minimum room cooling limit while in the event. Access Level: Installer Range: 50 to 100°F (10.0 to 38.0°C) Conditions: Y RELAY is set to HP or AC. Default: 50°F (10.0°C) COOL MINIMUM ROOM LIMIT Set the minimum room cooling limit while in the event. Access Level: Installer Range: 50 to 100°F (10.0 to 38.0°C) Conditions: Y RELAY is set to HP or AC and Default: 50°F (10.0°C) Schedules are in use or Scenes is set to All or Guest.
Set Temp Menu (4 of 4) Setting TEMPORARY HOLD Temperature adjustment in the home menu can result in either permanent temperature setting change or temporary temperature setting change that lasts 3, 6, 9, 12 hours or until the next scheduled event. Access Level: Installer Conditions: None FAN Set the minimum percentage the fan should operate while in the event. This provides ventilation for the building. Each 10% is 6 minutes per hour.
Time Menu (1 of 1) Setting Display MINUTES Select the current time minutes. Access Level: Installer, User Range: 00 to 59 Conditions: Always available. Default: 00 HOURS Select the current time hours. Access Level: Installer, User Range: 12 AM to 11 PM or 00 to 23 Conditions: Always available. Default: 12 AM DAY OF WEEK Select the current day of the week. Access Level: Installer, User Range: Sunday to Saturday Conditions: Always available. Default: Sunday MONTH Select the current month.
Schedule Menu (1 of 2) The schedule menu can operate on a 24 hour or 7 day repeating schedule. When a 24 hour schedule is selected, “SuMoTuWeThFrSa” is shown on the top of the screen to show that the event time applies to all days of the week. When a 7 day schedule is selected, each individual day of the week is shown with the event time. Setting EVENT 1 The first programmable schedule time period of the day. The temperature settings are used during this time period.
Schedule Menu (2 of 2) Setting Display SCHEDULE Select if the thermostat should change the temperature automatically using a programmable schedule. OFF = Programmable schedule is not used. Zone = Applies to this thermostat only. Master 1, 2, 3, 4 = In charge of one of four available network schedules. Member 1, 2, 3, 4 = Follows selected network schedule.
Display Menu (2 of 2) Setting BACKLIGHT Select how the display backlight operates. ON = Always full brightness. DIM = Dim when inactive, on when touched. DIM = Dim in , off in . On when touched. ON = On in , off in . On when touched. OFF = Off when inactive, on when touched. Access Level: Installer, User Conditions: Always available. Display Range: DIM, ON, DIM , ON , OFF Default: DIM SECONDARY ITEM Determine the default item in the upper right hand corner of the Home screen.
Monitor Menu (1 of 4) Setting Display ROOM AVERAGE Current room temperature. Displays the average if there are multiple room sensors. Range: -58 to 212°F Access Level: Installer (-50.0 to 100.0°C) Conditions: Sensor 1 or 2 is set to ROOM. Default: Not applicable. FLOOR AVERAGE Current floor temperature. Displays the average if there are multiple floor sensors. Access Level: Installer Conditions: Sensor 1 or 2 is set to FLOR.
Monitor Menu (2 of 4) Setting Display SENSOR 2 The temperature measurement from the sensor 2 input wiring terminals. Range: -58 to 212°F (-50.0 to 100.0°C) Access Level: Installer Conditions: Sensor 2 is set to ROOM, FLOR, or OUT. Default: Not applicable. HUMIDITY LOCAL The built-in relative humidity sensor measurement. Access Level: Installer Range: 0 to 100% Conditions: Humidity Sensor is set to On. Default: Not applicable. OUTDOOR HIGH The highest recorded outdoor air temperature measurement.
Monitor Menu (3 of 4) Setting Display FLOOR HIGH The highest recorded floor temperature measurement. Touch the number and the ENTER key to reset. Range: -76 to 149°F Access Level: Installer, User (-60.0 to 65.0°C) Conditions: Sensor 1 or 2 is set to FLOR. Default: Not applicable. FLOOR LOW The lowest recorded floor temperature measurement. Touch the number and the ENTER key to reset. Range: -76 to 149°F Access Level: Installer, User (-60.0 to 65.0°C) Conditions: Sensor 1 or 2 is set to FLOR.
Monitor Menu (4 of 4) Setting COOL W HOURS The total number of hours the W relay has been operated for radiant floor cooling. Touch the number and the ENTER key to reset. Access Level: Installer, User Conditions: Floor Cool is set to ON and W TERM is set to HRF1 or HRF2. FAN HOURS The total number of hours the fan has been operated. Touch the number and the ENTER key to reset. Access Level: Installer, User Conditions: G/O RELAY is set to FAN or ACC Relay is set to FAN.
Toolbox Menu (2 of 3) Setting Display STATUS INFO Toggles between “Status Info” and the current status including any overrides from the tekmarNet® system control. System Normal = Thermostat operating normally. Override W = The tekmarNet® system control is either forcing the W relay on or off. Cooling Floor = Floor cooling is in effect. WWSD = Warm Weather Shut Down is in effect. CWSD = Cold Weather Shut Down is in effect. Air Group Master Cool = The air group master thermostat is cooling.
Toolbox Menu (3 of 3) Setting Display DEVICE COUNT Provides a count of all the tekmarNet® thermostats and setpoint controls on the tekmarNet® system. Range: 1 to 24 Access Level: Installer Default: 1 Conditions: Must be connected to a tekmarNet® system. USER TEST Use the up or down arrow keys to select either the heat or cool test sequence, then press the NEXT key to begin. Press HOLD to pause at step for 5 minutes. Press NEXT to advance to the next step.
Setup Menu (1 of 7) Setting Display SENSOR 1 Select the auxiliary sensor input 1 type. Range: OFF, ROOM, FLOR (floor), COIL, DUCT Default: OFF Access Level: Installer Conditions: Always available. SENSOR 2 Select the auxiliary sensor input 2 type. Access Level: Installer Conditions: Always available. ROOM SENSOR Select whether the built-in room temperature sensor is on or off. Access Level: Installer Conditions: Only available when Sensor 1 or 2 is set to ROOM or FLOR.
Setup Menu (2 of 7) Setting Display W PUMP Select whether the primary or mix system pump on a tekmarNet® system control should operate while the first stage of heat W is operating. Access Level: Installer Range: OFF or ON ® Conditions: Only available when a tekmarNet system control is connected and W TERM is set to HRF1 or Default: ON HRF2 or connected to a tN2 Wiring Center. W THERMAL MOTOR Select whether the first stage of heat W operates a thermally actuated zone valve (wax actuator).
Setup Menu (3 of 7) Setting Display W2 PUMP Select whether the primary or mix system pump on a tekmarNet® system control should operate while W2 is operating. Access Level: Installer Range: OFF or ON Conditions: ACC RELAY is set to W2 and W2 TERMINAL Default: ON is set to CONV or COIL. W2 THERMAL MOTOR Select whether W2 operates a thermally actuated zone valve (wax actuator). When set to ON, there is a 3 minute delay before operating the pump and any heat sources.
Setup Menu (4 of 7) Setting Display Y MINIMUM OFF Select the compressor minimum off time. Access Level: Installer Range: 0:30 to 10:00 minutes Conditions: Y RELAY is set to AC or HP. Default: 5:00 minutes COOLING CWSD Select the outdoor temperature below which the cooling system is disabled. Range: OFF, 35 to 75°F (OFF, 1.5 to 24.0°C) Access Level: Installer Conditions: Y RELAY is set to AC or HP and the Default: 55°F (13.0°C) outdoor temperature is available.
Setup Menu (5 of 7) Setting Display W HEAT WWSD Select the outdoor temperature above which the radiant floor heating is shut off. Range: OFF, 32 to 80°F (0 to 26.5°C, OFF) Access Level: Installer Conditions: Two stage heating with the second stage being a heat pump, fan coil or a furnace and the outdoor temperature is available. W CYCLES PER HOUR Select the number of heating cycles per hour. SYNC = 20 minute zone synchronization. AUTO = Automatic cycles per hour to minimize temperature swings.
Setup Menu (6 of 7) Setting Display AIR GROUP MASTER Select if the thermostat is a master of an air group. Access Level: Installer Conditions: The thermostat must be connected to other thermostats using tekmarNet® and Y RELAY is set to HP or AC. AIR GROUP MEMBER Select if the thermostat is a member of an air group. Access Level: Installer Conditions: The thermostat must be connected to other thermostats using tekmarNet® and Y RELAY is set to OFF or HUM. PRIORITY Select either heating or cooling priority.
Setup Menu (7 of 7) Setting Display COOL PURGE Select the fan coil or furnace cooling purge based upon either time or on duct air temperature. Range: 0:00 to 3:00 minutes (no duct sensor) or Access Level: Installer OFF, 40 to 70°F (OFF, 4.5 to 21.0°C) (duct sensor required) Conditions: W or W2 is set to COIL or FURN. Default: 0:00 min or 60°F (15.5°C) FAN DELAY Select the time delay to allow the fan coil or furnace to warm up prior to activating the fan. This avoids blowing cold air.
Sequence of Operation Section A Heat and Cool Applications The 553 can operate in several different combinations of conventional and heat pump applications.
Warm Weather Shut Down-------------------------------------------------------------------When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD) setting on the tekmarNet® main control, the heating system is shut off. A W HEAT WWSD setting is available to allow a forced air heating system to heat the building while the radiant floor heat system is shut off during mild outdoor temperatures.
The first stage operates on a temperature differential of ±0.7°F (±0.4°C) centered around the heating setpoint. The second stage heat turns on when the temperature drops 0.7°F - W2 Differential setting below the heating setpoint. The second stage is shut off once the temperature reaches the heating setpoint. The second stage W2 is prevented from turning on until the first stage heat W or the heat pump operates for the elapsed time set by the W2 Delay setting. Auto provides the shortest wait time.
Section E Mode Operation The thermostat includes a mode key. Available modes are: • Heat - Allows heating • Cool - Allows cooling • Auto - Automatically switches between heating and cooling as necessary. The interlock time is applied when switching from heating to cooling or from cooling to heating. • Emergency - Only available when operating a heat pump. When set to Emergency the heat pump is locked out and the hydronic and backup heat are operated.
Section G Fan Operation The fan operates together with the air heating or cooling systems. The user can also select to operate the fan manually by pressing the Fan button. This allows the user to choose between Auto and On. “Auto” allows the fan to operate together with heating or cooling but normally the fan is off. “On” forces the fan to operate continuously.
The thermostat has three humidification modes. Mode Operation HM1 Stand Alone Humidifier Humidifier operates independently of the HVAC system. Available in all modes except off. HM2 Humidifier with Fan Humidifier ducted together with HVAC system. The system fan is operated whenever the humidifier is operating. This is only available when operating a conventional heating system with a fan. Available in all modes except off. HM3 Humidifier with Air Heating Humidifier ducted together with HVAC system.
Section I Air Group Operation In order to prevent heating and cooling at the same time, this thermostat can operate together with other thermostats on a tekmarNet® system to form an air group. On older model thermostats the air group functionality was previously described as a cool group. In an air group, one thermostat is assigned as the air group master. The air group master operates both the air heating and cooling equipment for the group. The 553 can be set to be a master or a member of the air group.
Section K Temperature Adjustment Permanent Adjustment - No Schedule --------------------------------------------When no programmable schedule is used, touch the up or down arrows to permanently set the “Set Heat Room” or “Set Cool Room” temperature. This thermostat is capable of controlling both air and floor temperature.
Section L Programmable Schedules Energy savings can be achieved by lowering the heating temperature and increasing the cooling temperature when the building is unoccupied or during the night. When operating on a programmable schedule, a or a symbol is shown in the home menu. The or indicates the current operating temperature. All schedules are stored in permanent memory and are not affected by a loss of power.
Section M Scenes (System Override) Scenes provide an easy way to save energy while away on vacation, or override a programmable schedule when plans change. --------------------------------------------------------------Away Key -----------------------------------This thermostat includes an Away Key to quickly turn down the heating temperatures and increase the cooling temperatures on all thermostats and suspend heating the domestic hot water tank to maximize energy savings.
Recommendation on How to Use Scenes -----------------------------------Choosing how to use scenes depends on the needs and lifestyle of the customer using the building. Multi-Tenant Apartments Scenes should be disabled (None) in multi-tenant buildings where each occupant has differing heating requirements. Residential Homes Some residential customers may not require scenes, in which case, scenes can be disabled (None).
Section O Access Levels The thermostat Toolbox menu supports four access levels: Installer (INST), User (USER), Limited (LTD), and Secure (SEC). The access level can be adjusted when the thermostat is unlocked. There are two locations to lock the thermostat: 1. Locally on the thermostat using the Lock switch located in the wiring area. 2.
Troubleshooting Error Messages (1 of 5) Error Message Description SETUP MENU SAVE ERROR The thermostat failed to read the Setup menu settings from memory and has reloaded the factory default settings. The thermostat stops normal operation until all settings in the Setup menu are checked except to provide freeze protection. To clear the error, set the access level to Installer and check all settings in the Setup menu.
Error Messages (2 of 5) Error Message Description DISPLAY MENU SAVE ERROR The thermostat failed to read the Display menu settings from memory and has reloaded the factory default settings. The thermostat continues to operate normally while displaying this error. To clear the error, set the access level to Installer and check all settings in the Display menu. tN2 PORT ERROR The thermostat has been connected to a tN2 zone already in use by a 2-stage zoning control.
Error Messages (3 of 5) Error Message Description DEVICE LIMIT More than 24 devices (thermostats or setpoint controls) have been connected to the tekmarNet® communication bus. To clear the error, remove and relocate devices to other available buses until the device count is 24 or less. ROOM SENSOR SHORT CIRCUIT ERROR Due to a short circuit, the thermostat is unable to read the built-in room temperature sensor.
Error Messages (4 of 5) Error Message Description SYSTEM CONTROL LOST ERROR The thermostat can no longer communicate to the tekmarNet® system control. Check for open or short circuits in the tekmarNet® communication wiring. The error automatically clears once the tekmarNet® system control has been detected. If the tekmarNet® system control was intentionally removed from the thermostat, remove and then re-apply power to clear the error.
Error Messages (5 of 5) Error Message Description ERROR AT THERMOSTAT There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this thermostat. 01 to 24 = Thermostat only network Go to the thermostat with the listed address to correct the error. ERROR AT THERMOSTAT There is an error on a different thermostat or setpoint control connected to the tekmarNet® system and not on this thermostat.
Limited Warranty and Product Return Procedure Limited Warranty The liability of tekmar under this warranty is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.