User Interface7.
Critical Settings8.
For a full list of settings and operational details, please refer to the thermostat Installation and Operation Manual (D552)
included with compatible tekmarNet
®
controls or download the brochure from www.tekmarcontrols.com
The following settings are essential to the successful operation of the system.
Step 1: Set switch setting #1 and tekmarNet
®
system control located in the mechanical room to Unlock to change Access
level to Installer. Return to Lock setting once installation has been completed.
Step 2: Press and hold “Home” button for 3 seconds to enter programming menus.
Step 3: Touch NEXT to locate the Setup Menu and touch ENTER.
Adjust
the Time.
Adjust the
Schedule.
Display the
Floor or Outdoor
temperature.
Away Key.
Turn the
Heat on
or Off.
Home Button.
Return to the ‘Home’
Screen from any menu.
Press and hold for 3
seconds to access the
programming menus.
Adjust the Temperature.
Room
Temperature.
Home
Button
Install Thermostat6.
Thermostat
Front
Push
Thermostat
Base
Setup Menu Settings
SENSOR 1
Select to the type of sensor connected to auxiliary sensor
input 1.
Range: OFF, ROOM, FLOR (floor), OUT (outdoor)
Default: OFF
SENSOR 2
Select to the type of sensor connected to auxiliary sensor
input 2.
Range: OFF, ROOM, FLOR (floor)
Default: OFF
ROOM SENSOR
Select whether the built-in room temperature sensor is on
or off.
Range: OFF or ON
Default: ON
W1 TERMINAL UNIT
Select the terminal unit type of the first stage of heat W1.
Range: CTRL, HRF1, HRF2, CONV, COIL, OTHR
Default: CTRL
Setup Menu Settings
W1 PUMP
Select whether the boiler system pump or mix system
pump on a tekmarNet
®
system control should operate
while the first stage of heat W1 is operating.
Range: OFF or ON
Default: ON
W1 THERMAL MOTOR
Select whether the first stage of heat W1 operates a
thermally actuated zone valve (wax actuator). When set
to ON, there is a 3 minute delay before operating the
pump and any heat sources.
Range: OFF or ON
Default: OFF
W CYCLES PER HOUR
Select the number of heating cycles per hour. Only
available when the thermostat is not connected to a
tekmarNet
®
System Control.
Range: SYNC, AUTO, 2 to 12
Default: SYNC