Wiring Guide

9 of 12 © 2008 W 444 - 12/08
System Pump Red wire or Terminal 4
The module includes two different methods to turn on a
system pump.
1. Powered output on back of module.
Connect 120 V (ac) to the black wire.
Connect the mix system pump to the red wire.
Connect the ground to the green wire.
Connect the neutral wire to the mix system pump.
Ensure that a wire nut is installed on the blue wire (if not
used).
24 V (ac) Power Terminals 2,3
Wire 24 V (ac) to terminals R and C.
If a Zone Manager is used:
Connect C on the 444 to C on the Zone Manager.
Connect R on the 444 to R on the Zone Manager.
Black
Red
Blue
Green
Pump
120 V (ac)
Neutral
System
Pump
Ground
L
If a 24 V (ac) transformer is used:
Connect C on the 444 to C on the transformer.
Connect R on the 444 to R on the transformer.
23
CR
Power
Transformer
Mix Supply Sensor (tekmar 082) Terminals 8, 9
Ensure the Mix Supply Sensor is either tie strapped to
the pipe or placed in a 1/2” OD immersion well.
The sensor should be located on the supply pipe between
the heating system and the mixing device.
Connect the two wires from the Mix Supply Sensor to
the Com and Mix (8 and 9) terminals.
89
Com Mix
-
2. 24 V (ac) output on the front of the module.
Connect the Sys Pmp terminal 4 to a Zone Manager
335 or 336 Pmp A input (terminal 3). Then wire the mix
system pump to the Zone Manager 335 zone group
pump A (terminals 30 and 31) or Zone Manager 336
zone group pump A (terminals 22 and 23).
Connect the Sys Pmp terminal 4 to a Dual Zone Manager
337 Pmp B input (terminal 3). Then wire the mix system
pump to the Dual Zone Manager 337 zone group pump
B (terminals 29 and 31).
Note: Ensure that a wire nut is installed on the Red wire
on the back of the module.
23
CR
Power
tN4 C Pmp tN1 C R
Zn Grp A
123456
Zone Manager
Pump
tN4 C Pmp
Zn Grp A A
123
Zn Grp
PmpA
N
4
Sys
Pmp
Zone
Manager
System
Pump