Wiring Guide

11 of 12 © 2008 W 444 - 12/08
Testing the System Pump Terminals 2, 4
The System Pump LED is green when the Pump contact
is energized.
If using the output on the back of the module:
Use a voltmeter to check for 120 V (ac) +/- 10% between
the Red wire and neutral.
If using the 24 V (ac) output on the front of the module:
Use a voltmeter to check for 24 V (ac) +/- 10% between
the Sys Pmp and the C terminals.
Testing tekmar Sensors Terminals 8, 9
To test the sensors, the actual temperature at each sensor
location must be measured.
Use a good quality digital thermometer with a surface
temperature probe for ease of use and accuracy. Where
a digital thermometer is not available, strap a spare
sensor alongside the one to be tested and compare the
readings.
Disconnect each sensor from the control.
Test the sensors resistance according to the instructions
in the sensor Data Brochure D 070.
Testing the Variable Speed Injection Pump Back of Module
Press the Test button on the tN4 System Control.
Once the Mix % Output reaches 100%, press the Test
button once again to pause the control at this output.
Measure the voltage on the variable speed injection
pump. The reading should be 120 V (ac) +/- 10%.
Press the Test button to resume the test sequence.
Note: At outputs below 100%, the electrical meter will not
read correctly.
If power is not present:
Measure the voltage on the Black wire and the neutral.
The reading should be 120 V (ac) +/- 10%.
If voltage is present on the Black wire but not on the Blue
wire, and the Mix % Output is 100%, then the internal
overload protection rated at 2.5 A may be damaged and
require repair. Contact your tekmar sales representative
for details on the repair procedures if this circuit is
damaged.
Testing the Floating Action Terminals 2, 5, 6
Press the Test button on the tN4 System Control.
When the Mix % Out is increasing, use an electrical
test meter to measure the (ac) voltage between the
C terminal 2 and Opn (Open) terminal 5. The reading
should be 24 V (ac) +/– 10%.
When the Mix % Out is decreasing, use an electrical
test meter to measure the (ac) voltage between the
C terminal 2 and Cls (Close) terminal 6. The reading
should be 24 V (ac) +/– 10%.
Testing the Analog V (dc) Signal Terminals 7, 8
Press the Test button on the tN4 System Control.
Once the Mix % Output reaches 100%, press the Test
button once again to pause the control at this output.
Set the multimeter to measure V (dc).
Connect the multimeter probes to the analog modulating
output terminals (7 and 8).
The reading should be near 10 V (dc).
Testing the Analog mA Signal Terminals 7, 8
Press the Test button on the tN4 System Control.
Once the Mix % Output reaches 100%, press the Test
button once again to pause the control at this output.
Remove the wires from the analog modulating output
terminals (7 and 8).
Set the multimeter to measure mA.
Connect the multimeter probes to the analog modulating
output terminals (7 and 8).
The reading should be near 20 mA.
Replace wires.