Wiring Guide

© 2008 W 441 - 12/08 6 of 8
Use a Phillips screwdriver to remove the two screws on the top of the actuating motor to remove the wiring cover.
All electrical wiring enters the actuating motor through the 1/2” (13 mm) conduit hole on the bottom. Standard 18 AWG
solid wire is recommended for all connections to the motor terminals.
When using conduit, a conduit wye is required to allow the separation of the sensor wires from the R, C, tN4 and Pump
wires.
Strip all wiring to a length of 3/8 in. or 10 mm for all terminals.
Refer to the current and voltage ratings at the back of this brochure before connecting devices to this control.
Caution: The mixing expansion module 441 is not suitable for use with rigid conduit.
24 V (ac) Power
Wire 24 V (ac) to terminals C and R.
If a Zone Manager is used:
Connect C on the 441 to C on the Zone Manager.
Connect R on the 441 to R on the Zone Manager.
If a 24 V (ac) transformer is used:
Connect C on the 441 to C on the transformer.
Connect R on the 441 to R on the transformer.
tN4 Communication
Wire the tN4 communication to terminals tN4 and C on the
desired tN4 mix temperature bus.
If a Zone Manager is used:
Connect tN4 on the 441 to Zone Group A or B tN4 on the
Zone Manager. The C terminal is already connected.
If a Zone Manager is not used:
Connect tN4 on the 441 to tN4 on another tN4 device
on the same mix tN4 bus.
Connect C on the 441 to C on another tN4 device on
the same mix tN4 bus.
441
Zone Manager
or
other tN4 device
tN4 C Pmp tN4 C R W
Zn Gp A A tNt Zone A1
1234
R C tN4 Pmp
441
Zone Manager
or
other tN4 device
tN4 C Pmp tN4 C R W
Zn Gp A A tNt Zone A1
1234
R C tN4 Pmp
System Pump
441
Zone Manager
or
other tN4 device
tN4 C Pmp tN4 C R W
Zn Gp A A tNt Zone A1
1234
R C tN4 Pmp
The 441 provides a 24 V (ac) powered signal to activate
a system pump. The system pump is powered off either a
Zone Manager Zone Group Pump or off a 24 V (ac) coil
Relay 003.
When connecting to a Zone Manager 335:
Connect the Pump terminal on the 441 to terminal 3
labeled Pmp A on the 335. This activates Zone Group
Pump A.
When connecting to a Zone Manager 336:
Connect the Pump terminal on the 441 to terminal 3 labeled Pmp A on the 336. This activates Zone Group Pump A.
When connecting to a Zone Manager 337:
Connect the Pump terminal on the 441 to terminal 3 labeled Pmp B on the 337. This activates Zone Group Pump B.
When using a Relay 003:
Connect the Pump terminal on the 441 to terminal 2 on the Relay 003.
Connect C on the 441 to terminal 7 on the Relay 003.
Line voltage is connected to terminal 8 on the Relay 003.
Switched line voltage for the pump is available on terminal 6 on the Relay 003.
Wiring the Control