Submittal Sheet

Job __________________________
Designer ______________________
Contact _______________________
www.tekmarcontrols.com  of 2 © 20 C 360 - 0/


0/
HVAC Systems
Replaces: New

Front View
Side View
2–7/8”
(72 mm)
1/2” Knock-out
(x 5 back) (x 5 bottom)
Mounting Base
CL
1/2”
(13 mm)
7/8”
(23 mm)
65/8
(170 mm)
7–5/8
(193 mm)
1–7/8” (49 mm)
1/2”
(14 mm)
Ø 3/16” (5 mm)

------------
Outdoor Temperature Reset
Indoor Temperature Feedback (with
optional indoor sensor)
Warm Weather Shut Down
Automatic Boiler Differential

----------------
Floating Action Mixing Control
Quick setup for easy installation and
programming of control
User comfort adjustment to increase or
decrease building space temperature
Advanced settings to fine-tune building
requirements
Powered mixing system pump output
Optional indoor sensor for room air
temperature control
Test sequence to ensure proper
component operation
Setback input for energy savings
20 V (ac) power supply
CSA C US certified (approved to applicable
UL standards)

-----------------------------------------------------
The Mixing Control 360 is designed to operate a mixing valve using Outdoor Temperature Reset. It can be used in applications ranging
from in-floor radiant to commercial baseboard systems for boiler protection with full reset. This control regulates a single heating water
temperature through Outdoor Temperature Reset. It controls the mixing by opening or closing a floating action type mixing valve
actuator (3 or 4 way valves), and also provides control of the mix system pump.

N / A
Floating Action
Literature D360, A360, D00, D070
Control Microprocessor control. This is not a safety (limit) control
Packaged weight 3. lb. (420 g)
Dimensions 6-5/8” H x 7-9/6” W x 2-3/6” D (70 x 93 x 72 mm)
Enclosure Blue PVC plastic, NEMA type 
Approvals
CSA C US, meets class B: ICES & FCC Part 5
Ambient conditions
Indoor use only, 32 to 04°F (0 to 40°C), RH ≤90% Non-
condensing
Power supply 20 V (ac) ±0%, 50/60 Hz, 300 VA
Floating output 24 V (ac) 0.34 A 8 VA
Relays 240 V (ac) 0 A /3 hp
Demand 20 to 260 V (ac) 2 VA
Sensors NTC thermistor, 0 kΩ @ 77°F (25°C ±0.2°C) ß=3892
Included Outdoor Sensor 070 and 2 of Universal Sensor 082
Optional tekmar type #: 033, 076, 077, 084
Warranty Limited 3 Year (See D360 for full warranty)
L N N Opn Cls Sw
Sys
Pmp
R R C UnO Com Boil Mix Com Out Indr
2
3 5 9 0 
4
6
7 8
2
3
4 5
6
7 8

Floating Action

Signal wiring must be
rated at least 300 V.
Use supply wires
suitable for 120°F
(50°C) above ambient
58033
Mixing Power Boiler
Demand
Advanced
Boiler Sensor
Installer
Supply
30% Enable
10% Enable
Return
Test
Terminal
Unit
Motor
Speed
Open Close
Mixing
Demand
Made in Canada by
tekmar Control Systems Ltd.
Power: 120 V ±10% 50/60 Hz 1300 VA
Floating Output: 24 V (ac) 0.34 A 8 VA
Relays: 240 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Demand: 20 to 260 V (ac) 2 VA
H1170C
Item
Powered Output
To increase or decrease the
building temperature.
• Press the Item, , buttons
simultaneously for 1 sec. to
enter the ADJUST menu
• Use the, , buttons to adjust
the ROOM setting
Display defaults back to VIEW
menu after 20 sec.
ROOM - Set to desired room temp.
OUTDR DSGN - Set to coldest (design)
outdoor temp.
Terminal Unit Set to
High Mass Radiant
Low Mass Radiant 2
Fan Coil 3
Convector 4
Radiator 5
Baseboard 6
Refer to brochure for more information
