Submittal Sheet
Job __________________________
Designer ______________________
Contact _______________________
www.tekmarcontrols.com of 2 © 20 C 356 - 0/
0/
HVAC Systems
Replaces: New
The Mixing Control 356 is designed to operate a mixing pump to control the temperature in a hot water heating system using outdoor
reset. It can be used in applications ranging from in-floor radiant to commercial baseboard systems for boiler protection with full reset.
This control regulates a single heating water temperature through outdoor reset. It provides mixing by speeding up or slowing down
a single permanent capacitor (standard wet rotor) circulator.
This control is designed to mount on a 2” x 4” electrical box. This control is designed to operate permanent capacitor, impedance
protected (standard wet rotor type) or equivalent pump.
------------
Outdoor Temperature Reset
Warm Weather Shut Down
Boiler control
Automatic Boiler Differential
Variable speed pump control
----------------
Quick setup for easy installation and
programming of control
User comfort adjustment to increase or
decrease building space temperature
Advanced settings to fine-tune building
requirements
Test sequence to ensure proper
component operation
CSA C US certified (approved to applicable
UL standards)
•
•
•
•
•
•
•
•
•
•
-----------------------------------------------------
Front View
1-7/8”
(48 mm)
Mixing Control 356
Variable Speed
Inst/Adv
Do not apply power
Com
Sup
Out
Boil
R+
C-
T
C US
Press & Release
Item + + , to adjust menu
Made in Canada
Signal wiring
must be rated
at least 300 V
Press & Hold
Item,
to view settings
, to test
Power:
Var. Pmp:
Relay:
H1193C
Terminal Unit
24 V
±
10% 50/60 Hz 3 VA
120 V (ac) 2.4 A 1/6 hp
120 V (ac) 5 A 1/6 hp
Mixing
Demand
10 30 50 70 90
Return Supply
% Out
Mixing Control 356
Variable Speed
1 2 3 4
5 6 7 8 9
VIEW
Item
MIX
Boiler
Power
tektra 911-02
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
2–7/8”
(74 mm)
4–3/4”
(120 mm)
Designed to mount on
2” x 4” electrical box
Variable Speed
Literature D356, A356, D00, D070
Control Microprocessor control. This is not a safety (limit) control
Packaged weight .5 lb. (670 g)
Dimensions 4-3/4” H x 2-7/8” W x 7/8” D (20 x 74 x 22 mm)
Enclosure White PVC plastic, NEMA type
Approvals
CSA C US, meets class B: ICES & FCC Part 5
Ambient conditions
Indoor use only, 32 to 04°F (0 to 40°C), RH ≤90% Non-
condensing
Power supply 24 V (ac) ±0%, 50/60 Hz, 3 VA
Var. pump 20 V (ac) 2.4 A (FLA), 5 A (LRA), /6 hp
Relays 20 V (ac) 5 A, /6 hp
Mixing demand 24 V (ac) 2 VA
Sensors NTC thermistor, 0 kΩ @ 77°F (25°C ±0.2°C) ß=3892
–Included Outdoor Sensor 070 and 2 of Universal Sensor 07
Warranty Limited 3 Year (See D356 for full warranty)
Side View
Back View